Technical information

4 – PARAMETERS
34
4.4.3 Protection Group
Group Display Description Setting Range Units Default Page
PFN 00 Jump Code Jump to parameter 1 – 18 1
PFN 01 Over Cur
Lvl
Over Current Level Off, 50 – 800 %FLA Off 58
PFN 02 Over Cur Tim Over Current Time Off, 0.1 90.0 Seconds 0.1 59
PFN 03 Undr Cur Lvl Under Current Level Off, 5 100 %FLA Off 60
PFN 04 Undr Cur Tim Under Current Time Off, 0.1 – 90.0 Seconds 0.1 60
PFN 05 Cur Imbl Lvl Current Imbalance Level Off, 5 – 40 % 15 61
PFN 06 Gnd Flt Lvl Ground Fault Level Off, 5 100 %FLA Off 62
PFN 07 Over Vlt Lvl Over Voltage Level Off, 1 40 % Off 63
PFN 08 Undr Vlt Lvl Under Voltage Level Off, 1 40 % Off 63
PFN 09 Vlt Trip Tim Voltage Trip Time 0.1 – 90.0 Seconds 0.1 64
PFN 10 Auto Reset Auto Reset Off, 1 900 Seconds Off 64
PFN 11 Ctrl Flt En Controlled Fault Stop Enable Off, On On 64
PFN 12 Indep S/R OL Independent Starting/Running Overload Off, On Off 65
PFN 13 Starting OL Motor Starting Overload Class Off, 1 – 40 10 66
PFN 14 Running OL Motor Running Overload Class Off, 1 – 40 10 42
PFN 15 OL H/C Ratio Motor Overload Hot/Cold Ratio 0 – 99 % 60 67
PFN 16 OL Cool Tim Motor Overload Cooling Time 1.0 – 999.9 Minutes 30.0 68
PFN 17 Reserved Reserved
PFN 18 Reserved Reserved