Technical information

4 – PARAMETERS
33
4.4 LCD Display Parameters
The 2x16 display has the same parameters available as the LED display, with the exception of two meter parameters instead of one
since two meters may be displayed on the main screen. The parameters are subdivided into five groups. The groups are QST (Quick
Start), CFN (Control Functions), I/O (Input/Output Functions), PFN (Protection Functions) and FUN (Function).
The Quick Start Group provides a collection of the parameters most commonly needed to be changed when commissioning a starter.
Many of the parameters in the Quick Start group are duplicates of the same parameters in other groups.
The following shows the menu structure for the LCD display as well as the text that is displayed for the parameters on the display.
4.4.1 Quick Start Group
Group Display Description Setting Range Units Default Page
QST 00 Jump Code Jump to parameter 1 – 9 1
QST 01 Motor FLA Motor FLA 1– 6400 RMS
Amps
10 41
QST 02 Motor SF Motor Service Factor 1.00 – 1.99 1.15 41
QST 03 Running OL Motor Running Overload Class Off, 1 – 40 10 42
QST 04 Local Src Local Source 43
QST 05 Remote Src Remote Source
Keypad
Terminal
Serial
Terminal
44
QST 06 Init Cur Initial Current 1 50 – 600 %FLA 100 45
QST 07 Max Cur Maximum Current 1 100 – 800 %FLA 600 46
QST 08 Ramp Time Ramp Time 1 0 – 300 Seconds 15 47
QST 09 UTS Time Up To Speed Time 1 – 900 Seconds 20 48
4.4.2 Control Function Group
Group Display Description Setting Range Units Default Page
CFN 00 Jump Code Jump to parameter 1 – 17 1
CFN 01 Start Mode Start Mode Voltage Ramp
Current Ramp
TT Ramp
Power Ramp
Current
Ramp
49
CFN 02 Ramp Time 1 Ramp Time 1 0 – 300 Seconds 15 47
CFN 03 Init Cur 1 Initial Current 1 50 600 %FLA 100 45
CFN 04
Max Cur 1 Maximum Current 1 100 800 %FLA 600 46
CFN 05 Ramp Time 2 Ramp Time 2 0 – 300 Seconds 15 57
CFN 06 Init Cur 2 Initial Current 2 50 600 %FLA 100 56
CFN 07 Max Cur 2 Maximum Current 2 100 – 800 %FLA 600 57
CFN 08 Init V/T/P Initial Voltage/Torque/Power 1 – 100 % 25 50
CFN 09 Max T/P Maximum Torque/Power 10 325 % 105 51
CFN 10 Kick Lvl 1 Kick Level 1 Off, 100 – 800 %FLA Off 52
CFN 11 Kick Time 1 Kick Time 1 0.1 – 10.0 Seconds 1.0 52
CFN 12 Kick Lvl 2 Kick Level 2 Off, 100 – 800 %FLA Off 57
CFN 13 Kick Time 2 Kick Time 2 0.1 – 10.0 Seconds 1.0 58
CFN 14 Stop Mode Stop Mode Coast
Volt Decel
TT Decel
Coast 53
CFN 15 Decel Begin Decel Begin Level 100 1 % 40 54
CFN 16 Decel End Decel End Level 50 – 1 % 20 55
CFN 17 Decel Time Decel Time 1 – 180 Seconds 15 56