Technical information

4 – PARAMETERS
31
Number Parameter Setting Range Units Default Page
P58 Miscellaneous Commands 0: None
1: Reset Run Time
2: Reset KWh/MWh
3: Enter Reflash mode
4 Store Parameters
5 Load Parameters
6: Factory Reset
0 78
P59 Communication Timeout OFF, 1 – 120 Seconds OFF 78
P60 Communication Baud Rate 1.2, 2.4, 4.8, 9.6, 19.2 Kbps 9.6 79
P61 Communication Drop Number 1 – 247 1 79
P62 Energy Saver OFF, On OFF 79
P63 Heater Level OFF, 1 – 25 %FLA OFF 80
P64 Starter Type nor: Normal
Id: Inside Delta
y-d: Wye-Delta
PctL: Phase Control
cFol: Current Follow
AtL: ATL
nor 81
P65 Rated Power Factor -0.01 (Lag)–1.00 (Unity) -0.92 82
P66 Rated Voltage 100, 110, 120, 200, 208, 220, 230,
240, 350, 380, 400, 415, 440, 460,
480, 500, 525, 575, 600, 660, 690,
1000, 1140, 2200, 2300, 2400,
3300, 4160, 4600, 4800, 6000,
6600, 6900, 10.00 (10000), 11.00
(11000), 11.50 (11500), 12.00
(12000), 12.47 (12470), 13.20
(13200), 13.80 (13800)
RMS
Voltage
480 82
P67 Phase Order InS Insensitive
AbC ABC
CbA CBA
SPH Single Phase
InS 83
P68 CT Ratio 72, 96, 144, 288, 864,
1320, 2640, 2880, 3900,
5760, 8000, 14.4 (14400), 28.8
(28800)
288 83