Technical information

4 – PARAMETERS
30
Number Parameter Setting Range Units Default Page
P39 DI 1 Configuration StOP
P40 DI 2 Configuration byP
P41 DI 3 Configuration
OFF: Off
FL
69
P42 R1 Configuration FLFS
P43 R2 Configuration run
P44 R3 Configuration
OFF: Off
FLFS: Fault (fail safe)
FLnF: Fault (non fail
safe)
run: Running
utS: UTS
AL: Alarm
rdyr: Ready
LOC: Locked Out
OC: Over Current
UC: Under Current
OLA: OL Alarm
ShFS: Shunt Trip (fail
safe)
ShnF: Shunt Trip (non
fail safe)
GfLt: Ground Fault
ES: Energy Saver
HEAt: Heating
utS
70
P45 Analog Input Trip Type OFF: Disabled
Lo: Low Level
Hi: High Level
OFF 71
P46 Analog Input Trip Level 0 – 100 % 50 72
P47 Analog Input Trip Time 0.1 – 90.0 Seconds 0.1 72
P48 Analog Input Span 1 – 100 % 100 73
P49 Analog Input Offset 0 – 99 % 0 74
P50 Analog Output Function 0: OFF (no output)
1: 0 – 200% Curr
2: 0 – 800% Curr
3: 0 – 150% Volt
4: 0 – 150% OL
5: 0 – 10 kW
6: 0 – 100 kW
7: 0 – 1 MW
8: 0 – 10 MW
9: 0 – 100% Ain
10: 0 – 100% Firing
11: Calibration
0 74
P51 Analog Output Span 1 – 125 % 100 75
P52 Analog Output Offset 0 – 99 % 0 75
P53 Inline Configuration OFF, 1.0 –10.0 Seconds 3.0 76
P54 Bypass Feedback Time 0.1 – 5.0 Seconds 2.0 76
P55 Keypad Stop Disable Enabled, Disabled Enabled 77
P56 Reserved
P57 Reserved