4 – PARAMETERS
29
4.3 LED Display Parameters
Number Parameter Setting Range Units Default Page
P1 Motor FLA 1 – 6400 RMS
Amps
10 41
P2 Motor Service Factor 1.00 – 1.99 1.15 41
P3 Motor Running Overload Class OFF, 1 – 40 10 42
P4 Local Source 43
P5 Remote Source
PAd: Keypad
tEr Terminal
SEr: Serial
tEr
44
P6 Initial Current 1 50 – 600 %FLA 100 45
P7 Maximum Current 1 100 – 800 %FLA 600 46
P8 Ramp Time 1 0 – 300 Seconds 15 47
P9 Up To Speed Time 1 – 900 Seconds 20 48
P10 Start Mode oLrP: Voltage Ramp
curr: Current Ramp
tt: TT Ramp
Pr: Power Ramp
curr 49
P11 Initial Voltage/Torque/Power 1 – 100 % 25 50
P12 Maximum Torque/Power 10 – 325 % 105 51
P13 Kick Level 1 OFF, 100 – 800 %FLA OFF 52
P14 Kick Time 1 0.1 – 10.0 Seconds 1.0 52
P15 Stop Mode CoS Coast
SdcL Volt Decel
tdcL TT Decel
CoS 53
P16 Decel Begin Level 100 – 1 % 40 54
P17 Decel End Level 99 – 1 % 20 55
P18 Decel Time 1 – 180 Seconds 15 56
P19 Initial Current 2 50 – 600 %FLA 100 56
P20 Maximum Current 2 100 – 800 %FLA 600 57
P21 Ramp Time 2 0 – 300 Seconds 15 57
P22 Kick Level 2 OFF, 100 – 800 %FLA OFF 57
P23 Kick Time 2 0.1 – 10.0 Seconds 1.0 58
P24 Over Current Level OFF, 50 – 800 %FLA OFF 58
P25 Over Current Time OFF, 0.1 – 90.0 Seconds 0.1 59
P26 Under Current Level OFF, 5 – 100 %FLA OFF 60
P27 Under Current Time OFF, 0.1 – 90.0 Seconds 0.1 60
P28 Current Imbalance Level OFF, 5 – 40 % 15 61
P29 Ground Fault Level OFF, 5 – 100 %FLA OFF 62
P30 Over Voltage Level OFF, 1 – 40 % OFF 63
P31 Under Voltage Level OFF, 1 – 40 % OFF 63
P32 Voltage Trip Time 0.1 – 90.0 Seconds 0.1 64
P33 Auto Reset OFF, 1– 900 Seconds OFF 64
P34 Controlled Fault Stop Enable OFF, On On 64
P35 Independent Starting/Running Overload OFF, On OFF 65
P36 Motor Starting Overload Class OFF, 1 – 40 10 66
P37 Motor Overload Hot/Cold Ratio 0 – 99 % 60 67
P38 Motor Overload Cooling Time 1.0 – 999.9 Minutes 30.0 68