Technical information
Table Of Contents

3 – KEYPAD OPERATION
Remote LCD Keypad and Display
24
Note: Run Hours 00:00 – 23:59
Run days 0 – 2730 or 7.5 years
kWatt Hours 0 – 999
MWatt Hours 0 – 9999
Starts 0 – 65535
3.3.6 Fault Log Screen
Pressing the MENU OR the LEFT arrow keys repeatedly cycles through all of the Parameter Groups either forward or reverse. More
information regarding each fault is available through the remote LCD display than is available through the standard LED display.
FL_: Fault__
NNNNNNNNNNNNN
FL _: = Fault Log Number. FL1 is the most recent fault and FL9 is the oldest fault.
Fault _ _ = Fault Code
NNN… = Fault Name, or the condition when the fault occurred
Pressing the UP and DOWN keys navigates through older and newer faults in the log.
Repeatedly pressing the ENTER key rotates through the conditions the starter was in when the fault occurred.
Enter
Step
1 Fault Description
2 Status when the fault occurred, Run, Stopped, Accel, etc
3 The average current at the time of the fault
4 The average voltage at the time of the fault
5 The line frequency at the time of the fault
3.3.7 Fault Screen
When a Fault occurs, the main screen is replaced with a fault screen. The screen shows the fault number and the name of the fault.
The main status screen is not shown until the fault is reset.
When a fault occurs, the STOP LED flashes.
Fault Number
Fault Name
NOTE: For a list of the Faults, refer to Appendix B – Fault Codes on page 148.
3.3.8 Lockout Screen
When a lockout is present, the word “Lockout” is displayed on the operate screen. Pressing the ENTER key displays more
information about the Lockout.
Lockout
Overload = 115%
Lockout
Control Power