Technical information

3 – KEYPAD OPERATION
Remote LCD Keypad and Display
20
3.3 2x16 Remote LCD Keypad
Like the standard keypad, the remote LCD keypad has the same basic functions with enhancements that allow using plain text instead
of codes and a menu structure instead of a straight line of parameters.
Additional keys have been added, such as “start”, “stop”, and a “left arrow” for moving the cursor around in the LCD display. Status
indicators have been added, providing additional information for the starter operation.
The remote keypad and display are connected to the MX control card via a 1 or 2 meter (3 or 6ft) cable. The remote keypad is
NEMA 1, 12, and 3R when mounted directly on a panel or the door of an enclosure with the correct gasket. If the bezel and keypad
are used, a NEMA 4 rating can be obtained. A keypad kit may be ordered from Benshaw if the starter was not originally ordered
with one. Part numbers are MX-1M-RKP-00 (includes a 1 meter cable) and MX-2M-RKP-00 (includes a 2 meter cable). Refer to
the hardware manual for mounting instructions.
Figure 8 – Remote LCD Keypad
s
s
t
t
a
a
r
r
t
t m
m
e
e
n
n
u
u
e
e
n
n
t
t
e
e
r
r
s
s
t
t
o
o
p
p
r
r
e
e
s
s
e
e
t
t
R
R
U
U
N
N
%
Min
kW
S
S
T
T
O
O
P
P
A
A
L
L
A
A
R
R
M
M
V
Hz
A
Starters
3.3.1 Description of the LEDs on the Keypad
The keypad provides three LED indicators in addition to the 2x16 character display. The LEDs provide starter status information.
Table 2 – 2x16 Remote Keypad LED Functions
LED State Indication
On Stopped STOP
Flashing Faulted
On Running and up-to-speed RUN
Flashing Running and not up-to-speed (ramping, decelling, brake, etc)
ALARM Flashing Alarm condition exists. If condition persists, a fault occurs
Note: By default, the Stop key is always active, regardless of selected control source (Local Source and Remote Source
parameters). It may be disabled though using the Keypad Stop Disable parameter. For more information refer to page