Technical information

3 – KEYPAD OPERATION
LED Keypad and Display
19
3.2.4 Restoring Factory Parameter Settings
To restore ALL parameters to the factory default settings, press and hold the PARAM and ENTER pushbutton switch on power up.
The display blinks “dFLt”. Parameters unique to the motor starter applications need to be set again to appropriate values before
motor operation.
3.2.5 Resetting a Fault
To reset from a fault condition, press RESET.
3.2.6 Emergency Thermal Reset
To perform an emergency thermal reset, press RESET and DOWN. This sets the motor thermal overload content to 0.