Technical information

10 – APPENDIX
164
LED LCD Parameter Setting Range Units Default Page Setting
P54 I/O 16 Bypass Feedback Time 0.1 5.0 Seconds 2.0 76
P55 I/O 17 Keypad Stop Disable Enabled, Disabled Enabled 77
Function Group
LED LCD Parameter Setting Range Units Default Page Setting
P69 FUN 01 Meter 1 Ave
Current
NA FUN 02 Meter 2
Ave Current
L1 Current
L2 Current
L3 Current
Curr Imbal
Ground Fault
Ave Volts
L1-L2 Volts
L2-L3 Volts
L3-L1 Volts
Overload
Power Factor
Watts
VA
VARS
kW hours
MW hours
Phase Order
Line Freq
Analog Input
Analog Output
Run Days
Run Hours
Starts
TruTorque %
Power %
Ave Volts
84
P68 FUN 03 CT Ratio 72, 96, 144, 288, 864,
1320, 2640, 2880, 3900,
5760, 8000, 14400, 28800
288 83
P67 FUN 04 Phase Order Insensitive
ABC
CBA
Single Phase
Insens. 83
P66 FUN 05 Rated Voltage 100, 110, 120, 200, 208,
220, 230, 240, 350, 380,
400, 415, 440, 460, 480,
500, 525, 575, 600, 660,
690, 1000, 1140, 2200,
2300, 2400, 3300, 4160,
4600, 4800, 6000, 6600,
6900, 10000, 11000,
11500, 12000, 12470,
13200, 13800
RMS
Voltage
480 82
P65 FUN 06 Rated Power Factor -0.01 (Lag) 1.00 (Unity) -0.92 82
P64 FUN 07 Starter Type Normal
Inside Delta
Wye-Delta
Phase Ctl
Curr Follow
ATL
Normal 81
P63 FUN 08 Heater Level Off, 1 – 25 %FLA Off 80
P62 FUN 09 Energy Saver Off, On Off 79
P61 FUN 10 Communication Drop Number 1 – 247 1 79