Technical information

10 – APPENDIX
163
LED LCD Parameter Setting Range Units Default Page Setting
P33 PFN 10 Auto Reset Off, 1 – 900 Seconds Off 64
P34 PFN 11 Controlled Fault Stop Enable Off, On On 64
P35 PFN 12 Independent Starting/Running
Overload
Off, On Off 65
P36 PFN 13 Motor Starting Overload Class Off, 1 – 40 10 66
P3 PFN 14 Motor Running Overload Class Off, 1 40 10 42
P37 PFN 15 Motor Overload Hot/Cold Ratio 0 – 99 % 60 67
P38 PFN 16 Motor Overload Cooling Time 1.0 – 999.9 Minutes 30.0 68
I/O Group
LED LCD Parameter Setting Range Units Default Page Setting
P39 I/O 01 DI 1 Configuration Stop
P40 I/O 02 DI 2 Configuration Bypass
Cnfrm
P41 I/O 03 DI 3 Configuration
Off
Stop
Fault High
Fault Low
Fault Reset
Bypass Cnfrm
E OL Reset
Local/Remote
Heat Disable
Heat Enable
Ramp Select
Fault Low
69
P42 I/O 04 R1 Configuration Fault FS
P43 I/O 05 R2 Configuration Running
P44 I/O 06 R3 Configuration
Off
Fault FS
Fault NFS
Running
UTS
Alarm
Ready
Locked Out
Overcurrent
Undercurrent
OL Alarm
Shunt Trip FS
Shunt Trip NFS
Ground Fault
Energy Saver
Heating
UTS
70
P45 I/O 07 Analog Input Trip Type Off
Low Level
High Level
Off 71
P46 I/O 08 Analog Input Trip Level 0 100 % 50 72
P47 I/O 09 Analog Input Trip Time 0.1 – 90.0 Seconds 0.1 72
P48 I/O 10 Analog Input Span 1 – 100 % 100 73
P49 I/O 11 Analog Input Offset 0 – 99 % 0 74
P50 I/O 12 Analog Output Function Off
0 – 200% Curr
0 – 800% Curr
0 – 150% Volt
0 – 150% OL
0 – 10 kW
0 – 100 kW
0 – 1 MW
0 – 10 MW
0 – 100% Ain
0 – 100% Firing
Calibration
Off 74
P51 I/O 13 Analog Output Span 1 – 125 % 100 75
P52 I/O 14 Analog Output Offset 0 99 % 0 75
P53 I/O 15 Inline Configuration Off, 1.0 10.0 Seconds 3.0 76