Technical information

10 – APPENDIX
157
Modbus Registers
Absolute Register
Address
Description R/W Range Units
30184/40184 LED Display Meter R/W 0: Status
1: Ave Current
2: L1 Current
3: L2 Current
4: L3 Current
5: Current Imbalance %
6: Ground Fault
7: Ave. Volts
8: L1-L2 Volts
9: L2-L3 Volts
10: L3-L1 Volts
11: Overload
12: Power Factor
13: Watts
14: VA
15: VARS
16: kW hours
17: MW hours
18: Phase Order
19: Line Frequency
20: Analog Input
21: Analog Output
22: Running Days
23: Running Hours
24: Starts
25: TruTorque %
26: Power %
-
30185/40185 LCD Display Meter 1 R/W Same as above but without 0 Status -
30186/40186 LCD Display Meter 2 R/W Same as above but without 0 Status -
30187/40187 Custom Stack Enable R/W 1: Disabled
0: Enabled
-
30188/40188 Starter Model Number R/W 0: None -
30189/40189 Miscellaneous Commands R/W 0: None
1: Reset Run Time
2: Reset kWh
3: Enter Reflash Mode
4 Store Parameters
5 Load Parameters
6 Factory Reset
-
30301/40301 Fault Code –
Most Recent Fault Log
Entry
R See the fault table in Appendix B -
30302/40302 Fault Code –
2nd Most Recent Fault
Log Entry
R -
30303/40303 Fault Code –
3rd Most Recent Fault
Log Entry
R -
30304/40304 Fault Code –
4th Most Recent Fault
Log Entry
R -
30305/40305 Fault Code –
5th Most Recent Fault
Log Entry
R -
30306/40306 Fault Code –
6th Most Recent Fault
Log Entry
R -
30307/40307 Fault Code –
7th Most Recent Fault
Log Entry
R -