Technical information

10 – APPENDIX
156
Modbus Registers
Absolute Register
Address
Description R/W Range Units
30167/40167 Analog Output Function R/W 0: Off (no output)
1: Ave. Current (0 – 200% FLA)
2: Ave. Current (0 – 800% FLA)
3: Ave. Voltage
(0 – 150% Rated)
4: Thermal Overload %
5: kW (0 – 10kW)
6: kW (0 – 100kW)
7: kW (0 – 1MW)
8: kW (0 – 10MW)
9: Analog Input
10: Output Voltage to Motor (based on
firing angle)
11: Calibrate (full 100% output)
-
30168/40168 Analog Output Span R/W 1 – 125 %
30169/40169 Analog Output Offset R/W 0 99 %
30170/40170 Inline Enable R/W 0: Disabled
1: Enabled
-
30171/40171 Inline Delay Time R/W 10 100 100 mSec
30172/40172 Bypass Feedback Time R/W 1 – 50 100 mSec
30173/40173 Keypad Stop Disable R/W 0: Disabled
1: Enabled
-
30174/40174 Reserved
30175/40175 Reserved
30176/40176 Reserved
30177/40177 Communication Timeout
Enable
R/W 0: Disabled
1: Enabled
-
30178/40178 Communication Timeout R/W 1 120 Sec
30179/40179 CT Ratio R/W 0: 72:1
1: 96:1
2: 144:1
3: 288:1
4: 864:1
5: 1320:1
6: 2640:1
7: 2880:1
8: 3900:1
9 5760:1
10: 8000:1
11: 14.4K:1
12: 28.8K:1
-
30180/40180 Energy Saver R/W 0: Disabled
1: Enabled
30181/40181 Heater Enable R/W 0: Disabled
1: Enabled
-
30182/40182 Heater Level R/W 1 – 25 % FLA
30183/40183 Starter Type R/W 0: Normal (Outside Delta)
1: Inside Delta
2: Wye-Delta
3: Phase Controller
4: Current Follower
5: Across the Line (Full Voltage)
-