Technical information

10 – APPENDIX
155
Modbus Registers
Absolute Register
Address
Description R/W Range Units
30145/40145 Ground Fault Trip Enable R/W 0: Disabled
1: Enabled
-
30146/40146 Ground Fault Level R/W 5 – 100 % FLA
30147/40147 Over Voltage Trip Enable R/W 0: Disabled
1: Enabled
-
30148/40148 Over Voltage Level R/W 1 40 %
30149/40149 Under Voltage Trip
Enable
R/W 0: Disabled
1: Enabled
-
30150/40150 Under Voltage Level R/W 1 40 %
30151/40151 Voltage Trip Time R/W
1 900
100 mSec
30152/40152 Auto Reset Enable R/W 0: Disabled
1: Enabled
-
30153/40153 Auto Reset Delay Time R/W
1 900 100 mSec
30154/40154 Controlled Fault Stop
Enable
R/W 0: Disabled
1: Enabled
-
30155/40155 DI 1 Configuration
30156/40156 DI 2 Configuration
30157/40157 DI 3 Configuration
R/W 0: Off
1: Stop
2: Fault High
3: Fault Low
4: Fault Reset
5: Bypass / 2M Feedback (F48)
6: Emergency Motor OL Reset
7: Local / Remote Control Source
8: Heat Disable
9: Heat Enable
10: Ramp Select
-
30158/40158 R1 Configuration
30159/40159 R2 Configuration
30160/40160 R3 Configuration
R/W
0: Off
1: Fault (fail safe)
2: Fault (non fail safe)
3: Running
4: Up To Speed
5: Alarm
6: Ready
7: Locked Out
8: Over Current Alarm
9: Under Current Alarm
10: Overload Alarm
11: Shunt Trip (fail safe)
12: Shunt Trip (non fail safe)
13: Faulted on Ground Fault
14: In Energy Saver Mode
15: Heating
-
30161/40161 Analog Input Trip Enable R/W 0: Disabled
1: Enabled
-
30162/40162 Analog Input Trip Type R/W 0: Low – Fault below preset level
1: High – Fault above preset level
-
30163/40163 Analog Input Trip Level R/W 0 – 100 %
30164/40164 Analog Input Trip Time R/W 1 – 900 100 mSec
30165/40165 Analog Input Span R/W 1 – 100 %
30166/40166 Analog Input Offset R/W 0 – 99 %