Technical information
Table Of Contents

10 – APPENDIX
154
Modbus Registers
Absolute Register
Address
Description R/W Range Units
30132/40132 Rated Voltage R/W 0: 100
1: 110
2: 120
3: 200
4: 208
5: 220
6: 230
7: 240
8: 350
9: 380
10: 400
11: 415
12: 440
13: 460
14: 480
15: 500
16: 525
17: 575
18: 600
19: 660
20: 690
21: 1000
22: 1140
23: 2200
24: 2300
25: 2400
26: 3300
27: 4160
28: 4600
29: 4800
30: 6000
31: 6600
32: 6900
33: 10000
34: 11000
35: 11500
36: 12000
37: 12470
38: 13200
39: 13800
Vrms
30133/40133 Phase Order R/W 0: Ins
1: ABC
2: CBA
3: SPH
-
30134/40134 Rated Power Factor R/W 1–100 -
30135/40135 Over Current Trip Enable R/W 0: Disabled
1: Enabled
-
30136/40136 Over Current Level R/W 50 – 800 % FLA
30137/40137 Over Current Time
Enable
R/W 0: Disabled
1: Enabled
-
30138/40138 Over Current Time R/W 1 – 900 100 mSec
30139/40139 Under Current Trip
Enable
R/W 0: Disabled
1: Enabled
-
30140/40140 Under Current Level R/W 5 – 100 % FLA
30141/40141 Under Current Time
Enable
R/W 0: Disabled
1: Enabled
-
30142/40142 Under Current Time R/W 1 – 900 100 mSec
30143/40143 Current Imbalance Trip
Enable
R/W 0: Disabled
1: Enabled
-
30144/40144 Current Imbalance Level R/W 5 – 40 %