Technical information

7 – TROUBLESHOOTING
107
The MX found the non-volatile parameter values to be corrupted.
Typically occurs when the MX is re-flashed with new software.
Perform a Factory Parameter reset and then properly set all parameters
before resuming normal operation.
F95 CPU Error – Parameter
EEPROM Checksum
Fault
If fault persists after performing a Factory Parameter reset, consult
factory.
F96 CPU Error The MX has detected an internal CPU problem. Consult factory.
F97 CPU Error – SW
Watchdog Fault
The MX has detected an internal software problem. Consult factory.
F98 CPU Error The MX has detected an internal CPU problem. Consult factory.
The non-volatile program memory has been corrupted. F99 CPU Error – Program
EPROM Checksum Fault
Consult factory. Control software must be reloaded in to the MX control
card before normal operation can resume.