Datasheet

8
I
L
I
PE
I
D
I
D
= I
PE
+ I
L
I
L
I
PE
I
D
I
D
= I
PE
+ I
L
©
B E N N I N G W o r l d C l a s s T e s t E q u i p m e n t
BENNING
ST 710
indication graphic display
protective conductor resistance
0.05 Ω – 20 Ω
insulation resistance
0.1 MΩ – 20 MΩ
(500 V DC)
protective conductor current/
contact current by means of
alternative leakage current
0.1 mA – 20 mA
measurement method
line test
R
PE
, R
ISO
, short–circuit test and continuity test of
phase conductor (L) and neutral conductor (N)
voltage 50 V – 270 V
scope of delivery carrying case, test cable with alligator
clip, appliance cable, battery set
item no. 050308
BENNING ST 710
Battery-operated Appliance Tester
ST 710
050309: with socket of type E (B/F/CZ/SK/PL)
050315: with socket of type CH (CH)
Scope of delivery BENNING ST 710
Test badges
Shock-proof socket onto
shock-proof plug for CM 9
16 A/32 A CEE coupling onto
CEE plug, 5-pin, for CM 9
Leakage
CM 9
Optional accessories for
BENNING ST 710/ST 725/ST 750 A
test badges “next test” (300 pieces)
item no. 756212
measuring adapters for three-phase loads (passive)
(
see page 19) item no. 044122/044123
leakage Current Clamp BENNING CM 9 for the measurement of
differential current, protective conductor current and load current of
single-phase and three-phase loads
(see page 7)
item no. 044065
measuring adapters for leakage current clamp BENNING CM 9
single-phase, conductors led through individually and with double insulation
shock-proof socket/shock-proof plug
item no. 044131
three-phase, conductors led through individually and with double insulation
16 A CEE coupling-CEE plug, 5–pin item no. 044127
32 A CEE coupling-CEE plug, 5–pin item no. 044128
See pages 18 + 19 for further accessories
Differential current measurement method with BENNING CM 9
Leakage current e.g. via
the water conduits and
capacity of the washing
machine to earth
indication=
(test sample under
operating conditions)
Features BENNING ST 710
• automatic testing procedure for devices of class I (key 1),
class II/III (key 2) and line test (key 3)
• testing of cable reels, multiple distributors and device
connecting cables with rubber connector
• measuring result with “pass/fail” information
• limiting values preset in compliance with DIN VDE standard
• indication of correct function key in case of incorrect oper-
ation and if the test sample is not switched on
• sufficient battery capacity (6 x 1.5 V, mignon, AA, IEC LR6)
for > 2500 test samples
• three-phase test objects can be tested by means of
optional measuring adapter
Measuring functions
• protective conductor resistance with a testing current of
200 mA DC and automatic polarity reversal
• insulating resistance with a testing voltage of 500 V DC
• protective conductor current and contact current by means
of alternative leakage current measurement method
• voltage measurement on external shock-proof socket (L-N,
L-PE, N-PE)
BENNING ST 710 Appliance Tester
mobile and network-independent testing of electrical appliances
BENNING ST 710
Battery-operated Appliance Tester for
mobile testing of electrical devices
• testing in compliance with EN 62638, ÖVE/ÖNORM E 8701,
NEN 3140
• easy - operation by means of three keys
• quick - complete testing within 10 seconds
• mobile - testing can be made network-independently
Application
Safety-related testing of electrical devices/work equipment
such as e.g. electrical devices/tools with ON/OFF switch,
motorized equipment, lamps, cable reels, multiple distributors
and household appliances. The protective conductor current/
contact current is measured by means of the alternative
leakage current measurement method.
Forms for test certificates for
Testing of electrical devices
are
available for download free of
charge at www.benning.de!
TRUE RMS