User manual
Chapter 7 Single Transfer Programming
64
ADVANCED MICRO CONTROLS INC.
Single Transfer Output Data
The format of the output data is shown in figure 7.1. Bits 0 - 7 control channel one and bits
10-17 control channel two. Note that these bits are numbered in octal. Bit addresses in the I/O
data tables are in octal.
17 16 15 14 12 11 10 07 06 05 04 03 02 01 0013
CHANNEL 1 CONTROL BITS
Start Move Profile
Stop Move Profile
Jog Up
Jog Down
External Jog Input Direction
"0" = up "1" = down
Enable Manual Jog
"0" = Disable "1" = Enable
RESERVED:
Must equal zero.
CHANNEL 2 CONTROL BITS
Start Move Profile
Stop Move Profile
Jog Up
Jog Down
External Jog Input Direction
"0" = up "1" = down
Enable Manual Jog
"0" = Disable "1" = Enable
RESERVED:
Must equal zero.
0000
Single Transfer Output Data
Figure 7.1 Single Transfer Output Data Format.