User manual

Chapter 3 Hardware Installation
ADVANCED MICRO CONTROLS INC.
39
Transducer Cable Installation
The transducer cable used with the 2762-17 module must be BELDEN 9731 or an exact
equivalent. Complete cables can be ordered from AMCI with the part number C2TT-(x) where
(x) is the length in feet. A wiring diagram of the C2TT-(x) cable is on the next page, figure 3.4.
If you plan to make your own cables, the required cable and connectors can be ordered from
AMCI. The AMCI part numbers are:
!
Belden 9731 -
Transducer Cable
!
MS-14 -
2762-17 Connector
!
MS-20 -
HTT Transducer Connector
The cable shields must be grounded at the 2762-17 Module
ONLY
!
The shields must not be connected to the transducer and must be
isolated from the raceway that the cable is installed in. Treat the shield
of the cable as a signal conductor. This practice will eliminate ground
loops that may induce EMI noise into the cable or damage the 2762-17
module.
CAUTION
!