User manual

Chapter 1 Introduction to the 2762-17
18
ADVANCED MICRO CONTROLS INC.
Jogging the Load Position
The 2762-17 allows you to manually jog the load position in one of three ways. From the
processor, the modules' keypad, or an external input. The motor runs at low speed when
jogging the position.
It is possible to jog the load past the upper or lower travel limits.
Jogging from the Processor
You jog the position from the processor by setting a bit in the output image table. Jog Up
and Jog Down bits are defined for each channel. The position will jog as long as the bit is set.
Jogging from the Keyboard
The 2762-17 has a separate menu for jogging the position. The module displays the current
position when in this menu. Press the [] or [] key to jog the position in the corresponding
direction. The position will jog as long as the key is pressed.
Jogging from the external input
The 2762-17 accepts a single input to jog the position. Bits in the output image table enable
the input and set the jogs' direction. Each channel has its own enable and direction bits.
It is possible to jog both channels simultaneously with the external input.
It is also possible to simultaneously jog the channels in opposite
directions.
The external input is opto-isolated and has the following electrical specifications.
!
Input Voltage: 10 to 24 Volts AC or DC.
!
Input Current: 10 mA required to turn input on.
CAUTION
!
CAUTION
!