User manual

Selectable default settings
48
VMD460-NA_D00001_01_M_XXEN/08.2013
df/dt Exit
Mode
off
on
off
Resp. value 0.1…9.9 Hz/s 1.0 Hz/s
Hysteresis 1.0…50 % 20%
Meas. window 0.05…1 s 200 ms
T (OFF) 0.04…30.0 s 100 ms
T (ON) 1 s…60 min 60 s
Asymmetry Exit
Mode off/on off
Resp. value 1.0…50.0 % 5.0 %
Hysteresis 1.0…50.0 % 20.0 %
T (OFF) 0.04…30.0 s 100 ms
Relay Exit
Relay mode
N/C
N/O
K1: N/C
K2: N/O
Digital Input* Exit
Relay mode
N/C
N/O
off
D1: N/C
D2: off
D3: N/O
D4: N/O
CEI 0-21 menu:
Settings
once twice
Factory
setting
*D1: Coupling switch K1
D2: Coupling switch K2 (Backup)
D3: local control