Datasheet
TDB103005en / Main catalogue part 1 – Insulation monitoring / 09.2011 43
1.3
A-ISOMETER® IR425
Operating elements Wiring diagram
1 - LED Power "ON", flashes in case of interruption of the connecting
leads E/KE or L1 / L2.
2 - Alarm LED "AL1", lights when the value falls below the set
response value Alarm 1 and flashes in case of interruption of
the connecting leads E/KE or L1/L2).
3 - Alarm LED "AL2", lights when the value falls below the set
response value Alarm 2 and flashes in case of interruption of
the connecting leads E/KE or L1/L2.
4 - LC display
5 - Test button "T": to call up the self test.
Arrow up button: Parameter change, to move up in the menu.
6 -
Reset button "R": to delete stored insulation fault alarms
Arrow down button: Parameter change, to move down in the
menu.
7 - "MENU" button: to call up the menu system.
Enter button: to confirm parameter change
1 - Supply voltage U
S
(see ordering information) via fuse
2 - Separate connection of E and KE to PE
3 - Connection to the IT system to be monitored:
AC: Connect terminals L1, L2 to conductor L1, L2.
DC: Connect terminal L1 to L+ and L2 to L-.
4 - Alarm relay K1: Alarm 1
5 - Alarm relay K2: Alarm 2
6 - Combined external test and reset button "T/R"
short-time pressing (< 1.5 s) = RESET
long-time pressing (> 1.5 s) = TEST
7 - Line protection by a fuse in accordance with IEC 60364-4-43
(6 A fuse recommended). In case of supply (A1/A2) from an
IT system, both lines have to be protected by a fuse.