Electrical connections
4 Electrical connections
B Allow mains cable to protrude at least 50 cm from 
wall.
B To maintain the splash-proof (IP) design: cut the 
cable grommet hole size to match the diameter of the 
cable, see fig. 27.
B The appliance must be earthed.
B It must be possible to completely isolate the appli-
ance with at least 3mm contact separation in both 
poles.
The wiring between the appliance and the electrical 
supply shall comply with current IEE Wiring Regulations 
(and any local regulations which apply) for fixed wiring 
to a stationary appliance.
• Supply: 230 V ~ 50 Hz, 150 Watts
• External fuse 3 A
• The system connected to the boiler must NOT have 
a separate electrical supply
• Water Protection IPX4D.
4.1 Connecting the appliance
To gain access to the mains connection remove the 
drop down facia cover. The drop down cover is 
removed by lowering it to the horizontal position and 
pushing firmly upwards at the rear of the supports to 
release the cover. Lift cover from the appliance. 
After installation (or in the event of an electrical fault) the 
electrical system shall be checked for short circuits, 
fuse failure, incorrect polarity of connections, earth con-
tinuity and resistance to earth.
B Pull out cover panel at the bottom and remove. Refer 
to fig. 25.
Fig. 25
B Remove screw and slide terminal cover forwards to 
remove. Refer to fig. 26.
Fig. 26
B Always disconnect the power supply to 
the appliance at the mains before carry-
ing out any work on the electrical sys-
tems and components.
0
1
2
3
4
5
E