Technical data
6 720 611 447 GB (03.11)
12
Installation
requirements of BS2767:10. 
Fit Thermostatic Radiator Valves to radiators in the 
sleeping accommodation and not to the radiator where 
the room thermostat is sited, this must be left open.
Repeated venting probably indicates a leak and this 
must be rectified to ensure the proper operation of the 
appliance.
No galvanised radiators or pipes must be used.
If any system water treatment is required then 
only products suitable for use with Aluminium 
shall be used i.e Fernox- Copal or Superconcen-
trate or Sentinal X100, in accordance with the 
manufacturers instructions. The use of any other 
substances will invalidate the guarantee. The pH 
value of the system water must be less than 8 or 
the appliance guarantee will be invalidated.
Suitable products are available from Betz-Dearborn Tel: 
0151-4209563, Fernox Tel: 01799-550811 and Sala-
mandor on 0121 378 0952.
A drain cock to BS2879 must be fitted to the lowest 
point of the system.
IMPORTANT: Check that no dirt is left in the 
water pipework as this could damage the appli-
ance. Thoroughly flush the heating system and 
the mains water supply before fitting the appli-
ance to the wall in accordance with the recom-
mendations of BS7593:1992. 
Fig. 5 Sealed primary water system
Fig. 6
3.4 Siting the appliance
Regulations concerning the Installation Site
B Relevant national regulations must be complied with 
section 3.9.1.
B Consult the installation instructions for details of min-
imum clearances required.
Combustion air
In order to prevent corrosion, the combustion air must 
not contain any corrosive substances.
Substances classed as corrosion-promoting include 
halogenated hydrocarbons which contain chlorine and 
fluorine compounds and are contained in some sol-
vents, paints, adhesives, aerosol propellants and house-
hold cleaners, for example.
Surface temperature
The max. surface temperature of the casing and the flue 
is less than 85 °C. 
This means that, no special safety precautions are 
required with regard to flammable building materials 
and fitted furniture. The specified clearances must be 
maintained.
Cupboard/Compartment 
The appliance can be installed in a cupboard/compart-
ment need for airing clothes providing that the require-
ments of BS6798 and BS5440:2 are followed. The low 
casing losses from the appliance eliminate the need for 
ventilation openings in the compartment.
6 720 610 576 -09.3O
APPLIANCE
A drain cock should be fitted at the lowest point of the
heating circuit and the appliance
WRC
approved
filling loop
Domestic
hot water
BS stop valve
Fixed spindle type.
Water main
Refer to
Appliance
Water Flow
Diagram
Lockshield valve
Radiator valve
Central heating return
Central heating flow