Specifications
9
Programming The Lock Duration (Function 5)
This is the duration the lock release will operate for when triggered by an access code
or by the ‘TRIG’ input. It is programmable in the range 0-99 seconds.
To program the lock duration use function 5:
L Move slide switch to ‘PGM’
L Type : 5(( <0-99> # e.g. 5( 7 # (7 seconds)
e.g. 5( 12 # (12 seconds)
L Observe red and green LEDs turn on briefly
L Move slide switch to ‘RUN’
Programming a Lock Delay Time (Function 6)
This function causes a delay (0-99 seconds) to be introduced between the triggering of
the lock release and its operation. Typically, this facility is used when the keypad is
located some distance from the entrance.
To program a Lock Delay Time:
L Move slide switch to ‘PGM’
L Type : 6(( <0-99> # e.g. 6( 3 # (3 second delay)
L Observe red and green LEDs turn on briefly
L Move slide switch to ‘RUN’
Programming The Alarm Duration (Function 7)
The alarm output is triggered by either a duress code or by a repeated entry of an
incorrect code. The Alarm duration determines the time for which this output is active
before automatically resetting. It is programmable in the range 0-99 seconds.
To program the alarm duration use function 7
L Move slide switch to ‘PGM’
L Type : 7(( <0-99> # e.g. 7( 60 # (60 seconds)
L Observe red and green LEDs turn on briefly
L Move slide switch to ‘RUN’