Submittal Sheet
Bell & Gossett
SUBMITTAL
A-128C
JOB:
REPRESENTATIVE:
UNIT TAG:
ORDER NO. DATE:
ENGINEER:
SUBMITTED BY: DATE:
CONTRACTOR:
APPROVED BY:
DATE:
Automatic Timer Kit
Model TC-1
Aquastat
Models: AQS-1/2, AQS-3/4
DESCRIPTION
TC-1 AUTOMATIC TIMER KIT
- To increase the overall efficiency
of a hot water recirculation system, the TC-1 timer control kit can be
installed for use on any B&G NBF/NRF/SSF circulator. The TC-1
timer control is programmable to turn the circulator ON and OFF
automatically at preset times. This permits the user to have the
pump circulate hot water only during those times when high usage
can be expected throughout the day.
AQS-1/2 and AQS-3/4 AQUASTAT
- are designed to
thermostatically turn any B&G NBF/NRF/SSF circulator ON and
OFF. The AQS-1/2 or AQS-3/4 will switch the pump OFF at 120ºF
(48.9ºC) and ON at 100ºF (37.8ºC). The aquastats are available in
separate models that will sense the temperature for either 1/2" o
r
3/4" copper pipe.
AUTOMATIC TIMER KIT and AQUASTAT COMBINATION
- The
automatic timer and aquastat kits can be used in combination.
When they are used together, the pump will only circulate wate
r
when the ON time conditions are met and when water temperature
is low enough to cause the aquastat to switch ON.
OPERATIONAL LIMITS
TC-1 AUTOMATIC TIMER KIT:
Power Supply: 115/120 VAC, 60 HZ, 1Ø
Minimum Switch Interval: 15 minutes
Run Modes: ON (continuous run), OFF (at all times),
TIMER (run at programmed intervals)
Maximum Switch Current: 16 amps
AQS-1/2, AQS-3/4 AQUASTATS
Thermostatic Switch Modes: OFF (open) at 120°F (48.9°C) wate
r
temperature and ON (closed) at 100°F (37.8°C) water temperature.
Thermostatic Element: Bimetal, senses surface temperature o
f
outside diameter of pipe.
Pipe Size: AQS-1/2 clips onto 1/2" copper pipe or 3/8" steel pipe
(OD of pipe 5/8"). AQS-3/4 clips onto 3/4" copper pipe or 1/2" steel
pipe (OD of pipe 7/8").
Mounting: May be installed to sense temperature at the suction o
r
discharge pipe of the pump.
CONSTRUCTION MATERIALS
TC-1 AUTOMATIC TIMER KIT:
Timer Body: Noryl Plastic
AQS-1/2, AQS-3/4 AQUASTATS:
Thermostat Covering: Epoxy (Environmentally Sealed)
Pipe Clip: Stainless Steel
Sensing Element: Bimetal
Wire Leads: Insulated 18" (457mm) #18 AWG
APPROX. SHIPPING WEIGHT
TC-1: 11oz. (.31Kg)
AQS-1/2: 5oz. (.14Kg)
AQS-3/4: 5oz. (.14Kg)
SCHEDULE
MODEL
NUMBER
PART
NUMBER
SIZE
INCHES
VOLTAGE RATING
60 HZ 1Ø
TAGGING INFORMATION QUANTITY
TC-1 113210 − 115-120
AQS-1/2 113223 1/2 115-120
AQS-3/4 113224 3/4 115-120