BALANCE VALVES Lead-Free* Circuit Setter
®
Plus
Specifications
MODEL
NUMBER
PART
NUMBER
SIZE
CONNECTION
TYPE
DIMENSIONS** in inches (mm)
WEIGHT
in lbs. (kg)
A B C
RF-
1
/2S LF 117410LF
1
/2" Sweat 2.91 (73.9) 1.82 (46.2) 2.85 (72.4) 0.6 (0.27)
RF-
3
/4S LF 117411LF
3
/4" Sweat 3.51 (89.2) 2.05 (52.1) 3.10 (78.7) 0.75 (0.34)
CB-
1
/2S LF 117412LF
1
/2" Sweat 2.91 (73.9) 1.82 (46.2) 2.85 (72.4) 1 (0.45)
CB-
3
/4S LF 117413LF
3
/4" Sweat 3.51 (89.1) 2.05 (52.1) 3.10 (78.7) 1.25 (0.6)
CB-1S LF 117401LF 1" Sweat 4.29 (109) 2.33 (59.2) 3.33 (84.6) 2 (0.91)
CB-1
1
/4S LF 117402LF 1
1
/4” Sweat 4.91 (124.7) 3.08 (78.2) 3.69 (93.7) 3.5 (1.6)
CB-1
1
/2S LF 117403LF 1
1
/2” Sweat 5.21 (132.3) 3.27 (83) 3.95 (100.3) 3.8 (1.7)
CB-2S LF 117404LF 2” Sweat 6.31 (160.3) 3.83 (97.3) 4.44 (112.8) 6.2 (2.8)
CB-
1
/2 LF 117414LF
1
/2" NPT 2.94 (74.7) 1.98 (50.3) 3.02 (76.7) 1.25 (0.6)
CB-
3
/4 LF 117415LF
3
/4" NPT 3.06 (77.7) 2.17 (55.1) 3.12 (79.2) 1.5 (0.7)
CB-1 LF 117416LF 1" NPT 3.81 (96.8) 2.47 (62.7) 3.42 (86.9) 2 (0.9)
CB-1
1
/4 LF 117103LF 1
1
/4” NPT 4.41 (112) 3.19 (81) 3.69 (93.7) 3.5 (1.6)
CB-1
1
/2 LF 117104LF 1
1
/2” NPT 4.42 (112.3) 3.37 (85.6) 3.95 (100.3) 3.8 (1.7)
CB-2 LF 117105LF 2” NPT 5.13 (130.3) 3.98 (101.1) 4.44 (112.8) 6.2 (2.8)
CB-2
1
/2 LF 117106LF 2
1
/2” NPT 6.00 (152.4) 4.51 (114.6) 4.83 (122.7) 9 (4.1)
CB-3 LF 117107LF 3” NPT 6.50 (165.1) 5.12 (130.0) 5.44 (138.2) 12 (5.4)
** All dimensions +/-0.125 (3.2 mm) tolerance. Dimensions are subject to change. Not to be used for construction purposes unless certified.
B
END VIEW
1
/2"-1"
TOP VIEW
1
/2"-1"
A
C
TOP VIEW 1
1
/4”-3”
END VIEW 1
1
/4”-3”
A
C
B
Save time, energy and water with the lead-free
Circuit Setter Plus and Circuit Setter Plus RF.
• Designed for all plumbing and HVAC systems.
• Provides equal ow throughout all circuits to
conserve water and optimize system efficiency.
• Calibrated accurate ow control and
measurement.
• Bi-directional design allows any installation
configuration.
• Externally adjustable manual balance
valve for easy adjustment.
• Reduces pump energy requirements.
• Meets or exceeds stringent codes for
potable water.
• Includes memory stop indicator.
• Provides drain option.
• Provides positive shut off and isolation.
• Includes pressure/temperature ports.
Description
The Circuit Setter Plus and Circuit Setter Plus RF
provide the perfect balance of adjustability and
efficiency for potable water and HVAC systems.
They are precisely calibrated for use as a
presettable balance valve, variable orifice flow
meter and positive shut-off service valve. They
are also designed for optimal system efficiency
and water conservation. The Circuit Setter Plus
and Circuit Setter Plus RF can provide the perfect
balancing solutions for your potable water and
HVAC system.
Construction
Body: Brass ASTM B283-C69300*
Ball: 304 Stainless Steel
Seat Rings: Glass and Carbon filled TFE
Readout Valves: Brass with EPT check valves
Stem “O” Ring: EPDM
Maximum Working Pressure
NPT Models: 400 PSIG (2758 kPa)
Sweat Models: See table below
Maximum Operating Temperature
-4°F (-20°C) to 250°F (121°C)
TYPE SOLDER
MAXIMUM PRESSURE LIMITATIONS
FOR 1/2” - 1” WITH SOLDER CONNECTIONS
PRESSURE PSI KPA TEMP ºF (ºC)
95-5
Tin-Antimony
300 (2068) 200 (93)
250 (1724) 225 (107)
200 (1379) 250 (121)
* Contains less than 0.25% lead content by weight on wetted surfaces.
CSA Certified: AB1953; Vermont S152; Maryland House Bill 372
(Statute 12-605). ANSI/NSF-61 Annex G Compliant.
CB-1LF