Instruction Manual
TECHNOFORCE Installation, Operation, and Maintenance
65
Appendix
Function Points # Point Range/ Modbus Units
Code Description Value Address
04 25 Speed % 0 to 100 30025 %
04 26 Lead Pump Number 1 to Pump # (in TechnoForce
User Setup Menu) 30026
04 27 Active Zone Number 1 to Zone # (in TechnoForce
User Setup Menu) 30027
7.5 TechnoForce Metasys N2 Comunication Points
NPT NPA Point Description Range/Value Units
BI 1 Pump #1 Failure 1 = Failure 0 = O.K.
BI 2 Pump #1 VFD Failure 1 = Failure 0 = O.K.
BI 3 Pump #1 Off Alarm 1 = Alarm 0 = O.K.
BI 4 Pump #2 Failure 1 = Failure 0 = O.K.
BI 5 Pump #2 VFD Failure 1 = Failure 0 = O.K.
BI 6 Pump #2 Off Alarm 1 = Alarm 0 = O.K.
BI 7 Pump #3 Failure 1 = Failure 0 = O.K.
BI 8 Pump #3 VFD Failure 1 = Failure 0 = O.K.
BI 9 Pump #3 Off Alarm 1 = Alarm 0 = O.K.
BI 10 Pump #4 Failure 1 = Failure 0 = O.K.
BI 11 Pump #4 VFD Failure 1 = Failure 0 = O.K.
BI 12 Pump #4 Off Alarm 1 = Alarm 0 = O.K.
BI 13 Pump #5 Failure 1 = Failure 0 = O.K.
BI 14 Pump #5 VFD Failure 1 = Failure 0 = O.K.
BI 15 Pump #5 Off Alarm 1 = Alarm 0 = O.K.
BI 16 Pump #6 Failure 1 = Failure 0 = O.K.
BI 17 Pump #6 VFD Failure 1 = Failure 0 = O.K.
BI 18 Pump #6 Off Alarm 1 = Alarm 0 = O.K.
BI 19 System Reset Required 1 = Yes 0 = No
BI 20 Pump #1 Enabled 1 = Enabled 0 = Disabled
BI 21 Pump #2 Enabled 1 = Enabled 0 = Disabled
BI 22 Pump #3 Enabled 1 = Enabled 0 = Disabled
BI 23 Pump #4 Enabled 1 = Enabled 0 = Disabled
BI 24 Pump #5 Enabled 1 = Enabled 0 = Disabled
BI 25 Pump #6 Enabled 1 = Enabled 0 = Disabled
BI 26 Pump #1 On/Off 1 = On 0 = Off
BI 27 Pump #2 On/Off 1 = On 0 = Off
BI 28 Pump #3 On/Off 1 = On 0 = Off
BI 29 Pump #4 On/Off 1 = On 0 = Off
BI 30 Pump #5 On/Off 1 = On 0 = Off
BI 31 Pump #6 On/Off 1 = On 0 = Off
BI 32 System Start/Stop 1 = Start 0 = Stop
BI 33 Analog Input #1 Failure 1 = Failure 0 = O.K.
BI 34 Analog Input #2 Failure 1 = Failure 0 = O.K.