7.4 TechnoForce MODBUS Communication Points
Function Points # Point Range/ Modbus Units
Code Description Value Address
02 1 Pump #1 Failure 1 = Failure 0 = O.K. 10001
02 2 Pump #1 VFD Failure 1 = Failure 0 = O.K. 10002
02 3 Pump #1 Off Alarm 1 = Alarm 0 = O.K. 10003
02 4 Pump #2 Failure 1 = Failure 0 = O.K. 10004
02 5 Pump #2 VFD Failure 1 = Failure 0 = O.K. 10005
02 6 Pump #2 Off Alarm 1 = Alarm 0 = O.K. 10006
02 7 Pump #3 Failure 1 = Failure 0 = O.K. 10007
02 8 Pump #3 VFD Failure 1 = Failure 0 = O.K. 10008
02 9 Pump #3 Off Alarm 1 = Alarm 0 = O.K. 10009
02 10 Pump #4 Failure 1 = Failure 0 = O.K. 10010
02 11 Pump #4 VFD Failure 1 = Failure 0 = O.K. 10011
02 12 Pump #4 Off Alarm 1 = Alarm 0 = O.K. 10012
02 13 Pump #5 Failure 1 = Failure 0 = O.K. 10013
02 14 Pump #5 VFD Failure 1 = Failure 0 = O.K. 10014
02 15 Pump #5 Off Alarm 1 = Alarm 0 = O.K. 10015
02 16 Pump #6 Failure 1 = Failure 0 = O.K. 10016
02 17 Pump #6 VFD Failure 1 = Failure 0 = O.K. 10017
02 18 Pump #6 Off Alarm 1 = Alarm 0 = O.K. 10018
02 19 System Reset Required 1 = Yes 0 = No 10019
02 20 Pump #1 Enabled 1 = Enabled 0 = Disabled 10020
02 21 Pump #2 Enabled 1 = Enabled 0 = Disabled 10021
02 22 Pump #3 Enabled 1 = Enabled 0 = Disabled 10022
02 23 Pump #4 Enabled 1 = Enabled 0 = Disabled 10023
02 24 Pump #5 Enabled 1 = Enabled 0 = Disabled 10024
02 25 Pump #6 Enabled 1 = Enabled 0 = Disabled 10025
02 26 Pump #1 On/Off 1 = On 0 = Off 10026
02 27 Pump #2 On/Off 1 = On 0 = Off 10027
02 28 Pump #3 On/Off 1 = On 0 = Off 10028
02 29 Pump #4 On/Off 1 = On 0 = Off 10029
02 30 Pump #5 On/Off 1 = On 0 = Off 10030
02 31 Pump #6 On/Off 1 = On 0 = Off 10031
02 32 System Start/Stop 1 = Start 0 = Stop 10032
02 33 Analog Input #1 Failure 1 = Failure 0 = O.K. 10033
02 34 Analog Input #2 Failure 1 = Failure 0 = O.K. 10034
02 35 Analog Input #3 Failure 1 = Failure 0 = O.K. 10035
02 36 Analog Input #4 Failure 1 = Failure 0 = O.K. 10036
02 37 General Alarm 1 = Alarm 0 = O.K. 10037
02 38 System Operation Mode 1 = Auto 0 = Manual 10038
05 1 Pump Sequence Alternation 1 = Yes 0 = No 00001
05 2 System Reset Request 1 = Yes 0 = No 00002
05 3 System Start / Stop 1 = Start 0 = Stop 00003