Instruction Manual
TECHNOFORCE Installation, Operation, and Maintenance
40
Operation
5. Operation
5.1 Normal Scrolling Operation
Other screens may be viewed by scrolling from the TechnoForce Pump Controller screen shown below:
<TECHNOFORCE PUMP>
CONTROLLER
MM/DD/YY HH:MM:SS A/P
STAT1 STAT2 STAT3
The STAT1 portion of the display indicates the current start/stop status of the system.
The STAT2 portion of the display indicates the current auto/manual mode of operation.
The following table indicates all possible options:
STAT2 Description Sections for Additional Information
AUTO Pump Controlled by Controller 5.2
MANUAL Pumps Controlled by User 5.4
The STAT3 portion of the display indicates the current alarm/event status. If NORMAL is displayed there are
no alarms. If ALARM or EVENT is displayed there are alarms/events that may prevent normal operation, refer
to Section 5.7 for additional information. In case of no ow shut down it displays *NFSD*.
Press the NEXT/ ( ) key. The display now shows:
< PUMP STATUS >
P1: RDY P2: N/A P3: N/A
P4: N/A P5: N/A P6: N/A
STAT1 STAT2 STAT3
Press the NEXT/ ( ) key. The display now shows:
<Seq 1-2 >
Sys = ### SP = ###
Suc = ### Spd = ###%
STAT1 STAT2 STAT3
Press the NEXT/ ( ) key. The display now shows:
< Power (KW) >
P1 :(#.#) P2: (#. #) P3 :( #. #)
P4 :(N/A) P5: (N/A) P6 :( N/A)
STAT1 STAT2 STAT3
Press the NEXT/ ( ) key. The display now shows:
< Current (A) >
P1 :(#.#) P2: (#. #) P3 :( #.#)
P4 :(N/A) P5: (N/A) P6 :(N/A)
STAT1 STAT2 STAT3
Press the NEXT/ ( ) key. The display now shows the following if the system is in MANUAL mode:
< >
Manual Speed: #%
STAT1 STAT2 STAT3
▲ ▲ ▲ ▲ ▲