4.10.44 High suction pressure
Paths: Status Screens / Set up(3) / AlrmEvt(5) / High Suction(5)
The High Suction Pressure menu is displayed below:
High Suct. Press: ##
High Suct Pr Tm: ##s Alarm: $
Alarm: $ Source: $$(AI/DI)
Reset Press: ## OK: $ (Y/N)
See following table for all HIGH SUCTION PRESSURE menu items.
High Suction Pressure Menu Items
Menu Item Variable Default Range Field
Value
High High Suct Press: ### 75 0-999
Suction
The pressure above which an alarm or event
Pressure
will be set for analog input method, in PSI.
High Suct Pr Tm: ###s 0 0-999
The proof timer prior to setting an alarm or event, in
seconds. A value of 0 disables this alarm.
Reset PSI: ### 67 0-999
The controller will automatically reset when the
suction pressure falls below the “Reset PSI”. Used for
analog input method only.
Alarm: $ N Y/N
Set this value to “Y” to consider high suction pressure
an alarm, or set it to “N” to consider it an event.
Source: $$
Select the desired value depending on the source. Use AI AI/DI
the (▲) Up and (▼) Down arrow keys to change the
source value
4.10.45 No ow shut down
Paths: Status Screens / Set up(3) / AlrmEvt(5) / NFSD(6)
The No Flow Shut Down menu is displayed below:
NFSD Tst Pr Tmr ###s
Min Spd . Pr Tmr ##s
Restart PSI Drop ##
Min Run ##m OK $(Y/N)