Menu Item Variable Default Range Field
Value
Loss2 : ### 0 0-999
The max loss in PSI that will be compensated for two pumps.
This value will be used to adjust the setpoint when two pumps
are running. This value will get subtracted from the setpoint as
a xed value when less than two pumps are running.
Loss3 : ### 0 0-999
The max loss in PSI that will be compensated for three pumps.
This value will be used to adjust the setpoint when three pumps
are running. This value will get subtracted from the setpoint
as a xed value when less than three pumps are running.
Loss4 : ### 0 0-999
The max loss in PSI that will be compensated for four pumps.
This value will be used to adjust the setpoint when four pumps
are running. This value will get subtracted from the setpoint
as a xed value when less than four pumps are running.
Loss5 : ### 0 0-999
The max loss in PSI that will be compensated for ve pumps.
This value will be used to adjust the setpoint when ve pumps
are running. This value will get subtracted from the setpoint
as a xed value when less than ve pumps are running.
Loss6 : ### 0 0-999
The max loss in PSI that will be compensated for six pumps.
This value will be used to adjust the setpoint when six pumps
are running. This value will get subtracted from the setpoint
as a xed value when less than six pumps are running.
4.10.24 Save/load menu
Paths: Status Screens / Set up(3) / System(3) / SaveLoad(12)
The Save/Load menu has been displayed below:
Selection: # 0=Exit
1=Save to Flash
2=Load from Flash
3=Load Default
Use the appropriate numeric key to select the appropriate menu desired, press the ENTER key. A detailed
description of each menu follows.
4.10.25 Save to ash
The Save To Flash screen is displayed below:
SAVE TO FLASH
Previously Saved Data
Will be overwritten!
PROCEED: $(Y/N)
Press YES and ENTER to save all of the user setup to the ash memory. Saving to ash will overwrite any data
that was previously saved. Saving to ash memory will save all setup information to the Flash PROM chip within
the controller
A load from ash will have to be performed to recover this saved data. See the following section.