Instruction Manual
TECHNOFORCE Installation, Operation, and Maintenance
16
Installation
RESYS MENU ITEMS
Menu Item Variable Default Range Field
Value
RESYS Active Sensor : ## 1 1-4
Enter the active system pressure sensor number
Drift Threshold: ##% 5 0-100
Pressure difference limit between the active and
redundant pressure sensor in %
Drift Pr Tm : ##s 0 0-999
Proof timer prior to give warning when exceed the
drift threshold limit, in seconds
To set up each eld, press the NO/0 key and then press the ENTER key.
The ACTIVE SENSOR eld will start blinking. Change the current value in Active Sensor eld by pressing
desired numeric Keys and then press ENTER key to conrm.
Press ENTER key to accept the current DRIFT THRESHOLD value. To change the value in DRIFT
THRESHOLD eld, press the desired Numeric Keys and then press ENTER to conrm.
Press ENTER key to accept the current value of DRIFT PR TM. To change the value in DRIFT PR TM
eld press the desired Numeric Keys and then press ENTER to conrm.
To accept the current values, press YES/7 key and then press ENTER key. The screen will go back to the
SENSOR SET UP menu displayed above.
Press the NEXT/( ) key if additional sensors need to be set up. Repeat the above steps for all remaining
sensors.
Pressing YES/7 key and then the ENTER key at the SENSOR SET UP screen will take the display back to
the MAIN SET UP screen.
4.10.1 Pump set up
Paths: Status Screens / Set up(3)
Press the SET PT/2 key at the Main Set Up menu screen. Then press the ENTER key.
The PUMP SET UP MENU will get displayed as shown below:
SELECTION: # 0= EXIT
1 = NUMBER OF PUMPS
2 = PUMP NAMEPLATE
3 = RESET PUMP TIME
To change the values in NUMBER OF PUMPS eld, press PV/1 key then press the ENTER key. The
following menu will get displayed:
TOTAL PUMPS: #
STANDBY PUMPS: #
OK $ (Y/N)
To set up each eld, press the NO/0 key and ENTER key. Modify the values as desired using the appropriate
numeric key. The pump number is limited to the maximum number of pumps.
To accept the current values, press YES/7 key and then press ENTER key.
The screen will go back to the PUMP SET UP MENU display.
To change the values in PUMP NAMEPLATE eld, press SET PT/2 key then press the ENTER key. The
following menu will get displayed:
<PUMP 1 NAMEPLATE>
AMPS: ###.# HP: ###.#
VOLTS: ### Hz: ##
Spd: #### OK $ (Y/N)
▲