Owner's manual

5. Press the Alternation key and observe the operation of each pump.
6. Close the running water faucet.
It is assumed that no demand for water is required. For example, no flow.
7. Observe the No Flow Shutdown sequence. All minimum run timers must elapse for
this sequence to occur.
8. Demand water from the system and observe the restart of the package.
If you encountered no problems, then you are done.
Commissioning, Startup, Operation, and Shutdown
TechnoForce and TechnoForce XLS Package System Mechanical Installation, Operation, and Maintenance
Manual