Owner's manual

Pumps
Every 30 days, the pump and motor shaft should be rotated by hand (10-15 turns)
to prevent bearing damage and potential for binding. Be sure shaft comes to rest
in different positions.
Close-coupled pumps may have minimal access to exposed shaft areas. In those
cases, care must be taken to avoid damage to the shaft though use of channel-
lock pliers or similar tools.
If removal of the coupling guard is required for hand-rotation of the pump and
motor shafts, this guarding must be reinstalled prior to removal of lock-out tag-out
and start-up.
Control Panels, VFDs, and Electronics
For storing electrical control panels, drives and other electrical items for more
than 3 months, insertion of moisture absorbing packets within the enclosure by be
necessary. Periodically replace as required. Remove packets prior to equipment
start-up.
Package Enclosures
Housing vents and/or openings will be sealed with plastic wrap and waterproof
tape.
Condensation protection shall be provided in accordance to instructions
previously noted.
PREPARATION FOR OPERATION
Remove all rust inhibitor from exposed machined surfaces using the method
described by the supplier.
Remove all corrosion protection devices or material from package.
Remove flange covers, tape, and all unnecessary pipe plugs.
Transportation and Storage
TechnoForce and TechnoForce XLS Package System Mechanical Installation, Operation, and Maintenance
Manual