Instructions / Assembly

Electrical connection checklist
Check that the following requirements are met:
The electrical wires are protected from high temperature and vibration.
The current type and power supply voltage connection must correspond to
the specifications on the name plate on the pump.
Use wires at least 14 AWG to supply power to the pump. Follow all local and
NEC wiring codes and practices.
The branch circuit supplying power to the pump shall be provided with a 15
Amps or less circuit breaker.
Attach appropriate sized electrical connector to one f the 7/8" diameter
holes on the side of the conduit box.
Connect ground wire to one of the ground screws inside the conduit box.
Make sure electrical connections are tightly secured before replacing the
motor cover.
The electrical control panel checklist
NOTICE:
The electrical supply must match the electrical rating of the
pump. Improper combination could fail to guarantee protection
of the unit.
Check that the following requirements are met:
The control panel circuit breaker is sized properly to protect the pump
against short-circuit.
These pumps are electronically thermally overload protected. No additional
overload protection is required.
The motor checklist
Electrical supply and grounding wires must be suitable for at least 194°F (90°C).
4.4 Pump installation requirements
Install the pump according to the liquid flow direction arrows.
Install the pump according to the allowed pump positions.
Make sure that the pump is adequately supported by the piping system and
properly aligned to eliminate any stress on the pump or the piping
Install the pump at a point closest to the highest static pressure point but
above the absolute lowest point in the system to avoid dirt and sediment
build-up.