When replacing an actuator, whether Belimo or other, be sure
to consider the application parameters before selecting the
replacement. The new product may not be the best fit for the
application. Example would be a Belimo AM24 US mounted
to a valve linkage. The direct replacement of the actuator is
AMB24-3. However, the AM24 US and the AMB24-3 are dif-
ferent lengths, the linkage would need to be replaced as well.
Instead of replacing the linkage the retrofit bracket Z-SMA and
Z-GMA can be used to extend the location of the anti-rotation
bracket to match the location of the anti-rotation bracket of
discontinued Belimo actuators.
Mounting Instructions
Retrofit Brackets [Z-SMA and Z-GMA]
2x
Replacing discontinued Belimo
Z-SMA for replacing AM and SM actuators