Install Instructions

17
71161-00001.F
G6/G7 Globe Valves with Single Mount AFX Actuators
Wiring Diagrams
BLK
Black
Negro
Noir
Preto
RED
Red
Rojo
Rouge
Vermelho
WHT
White
Blanco
Blanc
Branco
PNK
Pink
Rosado
Rosa
Cor-de ros
ORG
Orange
Anaranjado
Orange
Alaranjado
GRY
Gray
Gris
Gris
Cinzento
BLU
Blue
Azul
Bleu
Azul
BRN
Brown
Marron
Brun
Marrom
Master
Master
Amo
Maitre
Mestre
Slave
Slave
Esclavo
Esclave
Escravo
MFT95
Switch A Switch B Damper Position
Damper Open
Damper Closed
The direction of rotation switch is set so that the fail safe position and the
position of the damper is closed with no signal at wire R.
21
22
23
24
21
23
24
Blk (1) Common
Red (2) + Hot
Pnk
(4) W
Wht
(3) R
Gry
(5)
B
Org
(6)
‘U5’ Output 2 to 10 VDC
A
B
A
B
Line
Volts
Line
Volts
Line
Volts
24 VAC Transformer
24 VAC Transformer
135
Controller
-MFT95
-MFT95
W
R
B
Blk (1) Common
Red (2) + Hot
Pnk
(4) W
Wht
(3) R
Gry
(5) B
Org
(6)
‘U5’ Output 2 to 10 VDC
18
23
25
23
25
24
Line
Volts
Line
Volts
21
21
24 VAC Transformer
-MFT95
Blk (1) Common
Red (2) + Hot
Pnk
(4) W
Wht
(3) R
Gry (5) B
Org
(6)
‘U5’ Output 2 to 10 VDC
-MFT95
Blk (1) Common
Red (2) + Hot
Pnk
(4) W
Wht (3) R
Gry (5) B
Org
(6)
‘U5’ Output 2 to 10 VDC
To other
actuators
Resistor Kit No. ZG-R03
Series 90
Controller
Shunting
Resistor
W
R
B
No. of
actuators Resistance
2 140
3 71.5
4 47.5
5 37.5
6 28
18
22
22
23
25
23
25
23
25
23
25
24
21
21
Line
Volts
Line
Volts
24 VAC Transformer
-MFT95
Blk (1) Common
Red (2) + Hot
Pnk
(4) W
Wht (3) R
Gry (5) B
Org
(6)
‘U5’ Output 2 to 10 VDC
-MFT95
Blk (1) Common
Red (2) + Hot
Pnk
(4) W
Wht (3) R
Gry
(5) B
Org
(6)
‘U5’ Output 2 to 10 VDC
-MFT95
Blk (1) Common
Red (2) + Hot
Pnk
(4) W
Wht (3) R
Gry (5) B
Org
(6)
‘U5’ Output 2 to 10 VDC
-MFT95
Blk (1) Common
Red (2) + Hot
Pnk
(4) W
Wht
(3) R
Gry (5) B
Org
(6)
‘U5’ Output 2 to 10 VDC
Resistor Kit No. ZG-R06
No. of
actuators Resistance
2 1300
3 910
4 768
22
22
23
24
To other
actuators
Q209A
Minimum Position
Potentiometer
H205
Changeover
Controller
W973, W7100
Controller
Occupied
Contact
Honeywell T675A
Morning Warmup
Shuntin
g
Resistor
To other
actuators
Honeywell Q209A
Minimum Position
Potentiometer
Shunting
Resistor
Used with the W973 and W7100 controllers
Honeywell
T675A Morning
Warmup
W973, W7100
T775
W
W
W
R
R
R
Y
B
B
W
R
B
21
21
Line
Volts
Line
Volts
24 VAC Transformer
W
W
R
R
W
R
B
B
18
Override Wiring multiple actuators to a Series 90 Controller
22
21
23
24
Line
Volts
24 VAC Transformer
-MFT95
Blk (1) Common
Red (2) + Hot
Pnk
(4) W
Wht (3) R
Gry (5) B
Org
(6)
‘U5’ Output 2 to 10 VDC
Series 90 low limit control
135 for 0 to 50% control
280 for 0 to 100% control
Series 90
Controlle
r
W
W
R
R
B
B
18
22
22
23
24
Line
Volts
Line
Volts
21
21
24 VAC Transformer
25
23
25
-MFT95
Blk (1) Common
Red (2) + Hot
Pnk
(4) W
Wht
(3) R
Gry (5) B
Org
(6)
‘U5’ Output 2 to 10 VDC
-MFT95
Blk (1) Common
Red (2) + Hot
Pnk (4) W
Wht (3) R
Gry (5) B
Org (6)
‘U5’ Output 2 to 10 VDC
To other
actuators
Series 90
Controller
S963A
Minimum Position
Potentiometer
H205 Change-
over Controller
Occupied
Contact
Shunting
Resistor
W
W
W
R
R
R
B
B
B
18
Low Limit Control
22
21
23
24
Line
Volts
24 VAC Transformer
-MFT95
Blk (1) Common
Red (2) + Hot
Pnk
(4) W
Wht
(3) R
Gry (5) B
Org
(6)
‘U5’ Output 2 to 10 VDC
Series 90 high limit control - 280
Series 90
Controlle
r
W
W
R
R
B
B
18
High Limit Control Wiring Multiple Actuators to a Series 90 Controller
using Minimum Position Potentiometer
Typical Wiring Diagrams for Multiple Actuators
used with the W973, W7100 and T775
controllers
18
Actuators with plenum rated cable do not have numbers
on wires; use color codes instead.
21
Provide overload protection and disconnect as required.
22
Actuators and controller must have separate
transformers.
23
Consult controller instruction data for more detailed
information.
24
Resistor value depend on the type of controller and
the number of actuators. No resistor required for one
actuator. Honeywell
®
resistor kits may be used.
25
To reverse control rotation, use the reversing switch.
Notes: