Install Instructions
11
71161-00001.F
WGVL/G6/G7 Linkage with AVK Series Actuators
Wiring Diagrams
BLK
Black
Negro
Noir
Preto
RED
Red
Rojo
Rouge
Vermelho
WHT
White
Blanco
Blanc
Branco
PNK
Pink
Rosado
Rosa
Cor-de ros
ORG
Orange
Anaranjado
Orange
Alaranjado
BLU
Blue
Azul
Bleu
Azul
BRN
Brown
Marron
Brun
Marrom
Electronic Fail-Safe Actuator with -3
24 VAC Transformer
Line
V
olts
–
Blk (1) Common
Red (2) + Hot
Wht (3) +
Y
1
Input
Pnk (4)
2 3 18
Blk (1) – Common
Red (2) + Hot
Wht (3) Y
1
Input
Pnk (4) Y
2
Input
2
Line
V
olts
24 VAC Transformer
8
18
9
On/Off Floating Point
Blu (1)
Brn (2) +
Wht (3) +
Wht (4)
100 to 240 VAC
N L1
H L2
Line
Hot
A
2
A
Line N L1
Hot H L2
100 to 240 VAC
Blu (1)
Brn (2) +
Wht (3) +
Wht (4) +
2
50%
Signal
Direction
Fail
Postion
On/Off Floating Point Selector Switches
ComHot
Controller
Line
Volts
24 VAC Transformer
Blk (1) Common
Red (2) Hot
Wht (3) Y
1
Input
Pnk (4) Y
2
Input
+
5 10 18
ComHot
Controller
Line
Volts
24 VAC Transformer
Blk (1) Common
Red (2) Hot
Wht (3) Y
1
Input
Pnk (4) Y
2
Input
+
18
Blk (1) Common
Red (2) Hot
Wht (3) Y
1
Input
Pnk (4) Y
2
Input
ComHot
Controller
Line
Volts
24 VAC Transformer
Line
Volts
24 VAC Transformer
+
10 18
Triac Sink Triac Source Triac Sink with Separate Transformer
Electronic Fail-Safe Actuator with MFT
Blk (1) Common
Red (2) Hot
Wht (3) Y Input
Org (5) U Output
Line
Volts
24 VAC Transformer
2 to 10 VDC
Feedback Signal
(+)
(–)
3
18
Line
Volts
(–)
(+)
24 VAC Transformer
Blk (1) – Common
Red (2) + Hot
Wht (3) Y
1
Input
Pnk (4) Y
2
Input
Org (5) U Output
AB AB
Direction of rotation switch
A
B
Feedback Signal
2 to 10 VDC
2 18
8
9
Notes:
On/Off Floating Point
Blk (1) Common
Red (2) + Hot
Wht (3) Y
1
Input, 2 to 10 V
Org (5) U Output, 2 to 10 V
(–)
(+)
Line
Volts
24 VAC Transformer
Control Signal
VDC/mA
3
18
7
Ω
500
Ω
1/4 W
Functions
0%
50%
100%
Control mode acc. to Y
Min
Mid
Max
Normal
abc
500
Blk (1) Common
Red (2) + Hot
Org (5)
Wht (3) Y
1
Input, 2 to 10 V
(–)
(+)
Line
Volts
24 VAC Transformer (AC Only)
B
C
A
1/4 W
VDC/mA
Control Signal
18
7
Ω
Ω
VDC / 4 to 20 mA Override Control Min, Mid, Max Positions
Meets cULus requirements without the need of an
electrical ground connection.
A
Actuators with appliance cables are numbered.
2
Actuators may be connected in parallel. Power
consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
5
Only connect common to neg. (-) leg of control circuits.
7
A 500 Ω resistor converts the 4 to 20 mA control signal
to 2 to 10 VDC.
8
Control signal may be pulsed from either the Hot
(Source) or Common (Sink) 24 VAC line.
9
Contact closures A & B also can be triacs. A & B should
both be closed for the triac source and open for triac
sink.
10
For triac sink the Common connection from the actuator
must be connected to the Hot connection of the
controller. Position feedback cannot be used with a triac
sink controller. The actuator internal common reference
is not compatible.
12
IN4004 or IN4007 diode. (IN4007 supplied, Belimo Part
number 40155).
18
Actuators with plenum rated cable do not have numbers
on wires; use color codes instead.