Product Overview

Wiring Diagrams
INSTALLATION NOTES
Actuators may be connected in parallel. Power consumption and input
impedance must be observed.
Actuators may also be powered by 24 VDC.
A 500 resistor (ZG-R01) converts the 4 to 20 mA control signal to 2
to 10 VDC.
Control signal may be pulsed from either the Hot (Source) or Common
(Sink) 24 VAC line.
For triac sink the common connection from the actuator must be
connected to the hot connection of the controller. Contact closures A &
B also can be triacs. A & B should both be closed for the triac source
and open for triac sink.
Actuators with plenum cable do not have numbers; use color codes
instead.
Meets cULus requirements without the need of an electrical ground
connection.
!
WARNING! LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components.
Have a qualified licensed electrician or other individual who has been
properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to
live electrical components could result in death or serious injury.
Blk (1) - Common
Red (2) Hot
Wht (3) Y
1
Input
Org (5) U Output
Line
Volts
24 VAC Transformer
2 to 10 VDC
Feedback Signal
(+)
(–)
3
18
On/Off
Line
Volts
(–)
(+)
24 VAC Transformer
Blk (1) – Common
Red (2) + Hot
Wht (3) Y
1
Input
Pnk (4) Y
2
Input
Org (5) U Output
AB AB
Direction of rotation switch
A
B
Feedback Signal
2 to 10 VDC
2 18
8
9
Floating Point
Blk (1) - Common
Red (2) + Hot
Wht (3) Y
1
Input
Org (5) U Output
(–)
(+)
Line
Volts
24 VAC Transformer
Control Signal
VDC/mA
3
18
7
Ω
500
Ω
1/4 W
VDC / 4 to 20 mA
Functions
0%
50%
100%
Control mode acc. to Y
Min
Mid
Max
Normal
abc
500
Blk (1) - Common
Red (2) + Hot
Org (5) U Output
Wht (3) Y
1
Input
(–)
(+)
Line
Volts
24 VAC Transformer (AC Only)
B
C
A
1/4 W
VDC/mA
Control Signal
18
7
Ω
Ω
Override Control Min, Mid, Max Positions
LVX24-MFT
Modulating, Non-Spring Return, Linear, 24 V, Multi-Function Technology®
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
Date created, 11/09/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.