Accessories
Feedback Potentiometer P...A
For the non-spring return direct-coupled actuators
Application
The P…A feedback potentiometers are used with LR and AR actuators
to provide a resistive signal which varies with valve position.
The P…A units are applied with commercial proportional temperature
controllers to provide feedback of the valve position, or with electric or
electronic meters to provide position indication. The signal can also be
used as a positioner for parallel operation of multiple actuators.
Operation
The P…A feedback potentiometers are mounted onto the direct coupled
actuator. The switches are modular units that mount directly onto LR and
AR type actuators and are locked into place by guiding grooves on the
sides of the actuator.
A driver disk is attached to the actuator handle and offers direct
transmission of the actuator position to the micro switch cams.
Types
P140A Feedback Potentiometer 140 Ω
P200A Feedback Potentiometer 200 Ω
P500A Feedback Potentiometer 500 Ω
P1000A Feedback Potentiometer 1000 Ω
P2800A Feedback Potentiometer 2800 Ω
P5000A Feedback Potentiometer 5000 Ω
P10000A Feedback Potentiometer 10000 Ω
Technical Data P...A
Resistance Values As Above
Output 1 W
Tolerance ± 5%
Linearity ± 2%
Resolution Min. 1%
Residual Resistance max. 5% On Both Sides
Electrical Connection 3 ft, 18 GA Appliance Cable
½" Conduit Connector
Humidity
5 to 95% RH non-condensing
Ambient Temperature -22°F to 122°F [-30°C to 50°C]
Storage Temperature -40°F to 176°F [-40°C to 80°C]
Housing
NEMA 2 / IP54
Housing Rating UL94-5VA
Servicing
Maintenance Free
Agency Listings cULus acc. to UL60730-1
CE according to 73/23/EEC
Quality Standard ISO 9001
Weight 4.6 oz [130 g]
Wiring Diagram
Mounting Instructions
1. Press down the manual override button and rotate the
actuator fully counter clockwise.
2. Place the switch/potentiometer adaptor onto the hex shaft of the
handle which is in the center of the valve/actuator coupling.
3. Slide switch onto the actuator using the actuator guiding grooves
on the sides of the actuator.
4. Check for correct mating of the adaptor to the switch.
5. Adjust switch dials as necessary.