Install Instructions
Table Of Contents
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
31
Di
mens
i
ons (Inches [mm])
CCW
CCW
CCW
CCW
CW
CW
CW
CW
I
nsta
ll
at
i
on
I
nstruct
i
on
s
Q
uick-Mount Visual Instructions
f
or Mechanical Installatio
n
Quick-Mount Visual Instructions
1
. Rotate the damper to its fail-safe position
.
If the shaft rotates counterclockwise, mount the “
CC
W” side of the actuator out
.
If it rotates clockwise, mount the actuator with the “
C
W” side out.
2. If the universal clamp is not on the correct side of the actuator, mount it onto the correct side
.
3
.
S
lide the actuator onto the shaft and tighten the nuts on the V-bolt with a 10mm wrench to 6-8 ft-lb of torque
.
4
. Slide the anti-rotation strap under the actuator so that it en
g
a
g
es the slot at the base of the actuator. Secure the strap to the duct work with #8 self-tappin
g
screws
.
NO
TE: Read the “
S
tandard Mounting” instructions, on the next page, for more detailed information
.
min. 3 1/2” [90]
min. 3/4” [20]
.2
.8
CCW CW
35° ... 95°
9
1/
4"
[
6.35 mm
]
1/
4" [6.35 mm
]
1/
4" [6.35 mm
]
1
/
4" [6.35 mm
]
M40024 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc
.