User Guide

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
31
Multi-Function Technology
®
SY-MFT
Programmable Code Loss of Control Signal Input Signal Feedback Output Signal
ACE
stop 2…10V U5 U5 2...10V
ACF
stop 0.5…10V U5 U5 0.5...10V
ACG
stop 4…20mA U5 U5 4…20mA
ACH
stop 4…20mA U5 U5 2...10V
ACJ
open 2…10V U5 U5 2...10V
ACK
open 0.5…10V U5 U5 0.5...10V
ACL
open 4…20mA U5 U5 4…20mA
ACM
open 4…20mA U5 U5 2...10V
ACN
close 2…10V U5 U5 2...10V
ACP
close 0.5…10V U5 U5 0.5...10V
ACR
close 4…20mA U5 U5 4…20mA
ACS
close 4…20mA U5 U5 2...10V
W3E**
stop 0.02-5.00 seconds PWM U5 U5 2...10V
Note: Runtime is fixed based on actuator model.
**Available only on -24MFT models.
M40035 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc.