Datasheet
TECHNICAL DATA SHEET
code
70007E
version
5
2x2xAWG 22/7 (QUAD)
date
2016-03-10
PROFINET TYPE B PVC
page
2/2
Belden Wire & Cable B.V.
All rights are reserved. Reproduction in whole or in part is prohibited without the written consent of the copyright owner
REQUIREMENTS AND TEST METHODS
Electrical:
ISO/IEC 11801 ed. 2.0, Cat.5e.
Max. operating voltage UL 300 V rms
Test voltage wire-wire/wire-screen 2.5kVdc
Maximum conductor DC-resistance @ 20˚C 57.1 Ω/km
Transfer impedance @ 10MHz < 10 mOhm/m
Nom. velocity of propagation 68 %
Delay < 5.3 ns/m
Impedance @ 1 – 100 MHz 100 +/- 15 Ω
Frequency
(MHz)
Nom.
Attenuation
(dB/100m)
Min.
Next
(dB)
Min.
ELFEXT
(dB/100m)
Min.
SRL
(dB)
1
2.1
65
.3
64
-
4 4.1 56.3 52 23
10 6.5 50.3 44 25
16 8.3 47.2 40 25
31.25 11.7 43 34 23.6
62.5
17.0
38
.4
28
21.5
100
22.0
35
.3
24
20.1
Mechanical and physical:
Flame resistance IEC 60332-1
Oil resistance IEC 60811-2-1
Temperature range installing - 15 to +60 ˚C
Temperature range operating - 40 to +80 ˚C
Temperature range storage -40 to +80 ˚C
Flame resistance UL AWM Cable flametest
UL AWM Style 2464
Belden declares this product to be in compliance with the environmental regulations EU RoHS (Directive 2002/95/EC, 27 January 2003);