Specifications
Technical description
30 DRYPOINT RA 80 – 720
DATABASE
Below is a list of the parameter description, type and address of data on DMC20 :
Data
Description
Type
Register
Address
DewPoint DewPoint temperature - T1 probe Signed Integer
0000 - R
Air →O
Temperature of the incoming air - T2 probe Signed Integer
0001 - R
Air ←O
Temperature of the outgoing air - T3 probe Signed Integer
0002 - R
Compr.LP Suction temperature of the compressor (low pressure side) - T4 probe Signed Integer
0003 - R
Compr.HP Outlet temperature of the compressor (high pressure side) - T5 probe Signed Integer
0004 - R
Condens. Condensing temperature - T6 probe Signed Integer
0005 - R
Water →O
Inlet temperature of the cooling water (Water-Cooled) - T8 probe Signed Integer
0006 - R
Ambient Ambient temperature - T7 probe Signed Integer
0007 - R
Language
1)
Selection of the language for dialogue and alarm messages Signed Integer
0200 - R/W
DewPoint Set Not Used Signed Integer
0201 - R/W
Diff. DewPoint Not Used Signed Integer
0202 - R/W
E Drain Time Not Used Signed Integer
0203 - R/W
E Drain Pause Not Used Signed Integer
0204 - R/W
S Drain Time Not Used Signed Integer
0205 - R/W
S Drain Pause Not Used Signed Integer
0206 - R/W
Display Contrast. Adjustment of the Display contrast Signed Integer
0207 - R/W
Min DewPoint Not Used Signed Integer
0208 - R/W
Max DewPoint Not Used Signed Integer
0209 - R/W
Low DewPoint Temperature of interv. for the too low DewPoint alarm Signed Integer
0210 - R/W
Low DP Diff.! Differential temperature for the too low DewPoint alarm Signed Integer
0211 - R/W
Low DP Delay! Delay time for the too low DewPoint alarm Signed Integer
0212 - R/W
High DewPoint ! Temperature of interv. for the too high DewPoint alarm Signed Integer
0213 - R/W
High DP Diff.! Differential temperature for the too high DewPoint alarm Signed Integer
0214 - R/W
High DP Delay! Delay time for the too high DewPoint alarm Signed Integer
0215 - R/W
Condensation ! Temperature of intervention for the too high DewPoint alarm Signed Integer
0216 - R/W
Condens.Diff.! Differential temperature for the too high DewPoint alarm Signed Integer
0217 - R/W
Condens.Delay! Delay time for the too high DewPoint alarm Signed Integer
0218 - R/W
Peripheral No Unit address for serial communication Signed Integer
0219 - R/W
Working Operating time of the dryer in hours Signed Integer
0246 - R/W
Alarm STOP Presence of an alarm that has stopped the dryer bit - 1=Yes
0100.0 - R
Alarm Status Presence of an alarm bit - 1=Yes
0100.1 - R
Cond. Fan Switch Status of the condenser fan control pressure switch bit - 1=ON
0101.3 - R
Remote ON/OFF
Switch
Status of the Remote ON/OFF switch bit - 0=Local
1=Remote
0101.6 - R
DewPoint LOW Low DewPoint alarm ON bit - 1=Yes
0102.0 - R
DewPoint HIGH High DewPoint alarm ON bit - 1=Yes
0102.1 - R
Condens. HIGH High Condensation temperature alarm ON bit - 1=Yes
0102.2 - R
STOP Compr.LP Cooler low pressure switch (P
B
) alarm ON bit - 1=Yes
0102.4 - R
STOP Compr.HP Cooler high pressure switch (P
A
) alarm ON bit - 1=Yes
0102.5 - R
Protection Fan. Fan thermal/electrical protections alarm ON (Air-Cooled) bit - 1=Yes
0102.6 - R
Protection Comp. Compressor thermal/electrical protections alarm ON bit - 1=Yes
0102.7 - R
Probe Fault Probe faulty alarm ON bit - 1=Yes
0102.8 - R
Stop ! Low DP STOP enabled in case the DewPoint of the dryer is too low bit - 1=Yes
0220.0 - R/W
Stop ! High DP STOP enabled in case the DewPoint of the dryer is too high bit - 1=Yes
0220.1 - R/W
Automatic Start-up Machine enabled to restore its operation after a power black out bit - 1=Yes
0220.2 - R/W
Recovery After !
Autom.
Automatic alarms reset bit - 1=Yes
0220.3 - R/W
ON/OFF DMC20 Status of DMC20 - ON or OFF (Stand-by) bit-1=Stand-by
0220.15 -
R/W
NOTE
:
1)
Language selection : 00=Italian - 01=English - 02=German - 03=French
R=Read - W=Write