Specifications

Technical Specifications
DRYPOINT RA 80 – 720 17
4.3. Technical Specifications DRYPOINT RA 80-160 /WC
160
16000
960
565
0.15
1.40
0.37
0.56
1940
3.7
2850
4.8
166
140
14500
870
512
0.13
1.30
0.36
0.54
1790
3.5
2250
4.6
155
120
12500
750
441
0.07
G 2.1/2”
1.15
0.27
0.41
G 3/4”
1390
2.8
1840
3.7
146
100
10500
630
371
0.13
1.00
0.26
0.40
1290
2.4
1670
2.9
99
Water-Cooled
80
8100
486
286
+3 equal to 0.73 g/m
3
of H
2
O
+25 (+50)
+1
+35 (+70)
7
14
0.09
G 2”
R404A
0.95
-
0.24
0.36
Automatic by valve
30
3 (10)
G 1/2”
3/400-415/50
1190
2.2
1590
2.7
< 70
97
[l/min]
[m
3
/h]
[scfm]
C]
C]
C]
C]
[barg]
[barg]
[bar]
[BSP-F]
[kg]
[m
3
/h]
[m
3
/h]
[m
3
/h]
C]
[barg]
[BSP-F]
[Ph/V/Hz]
[W]
[A]
[W]
[A]
[dbA]
[kg]
DRYPOINT RA MODEL
Air flow rate at nominal condition
1
Pressure DewPoint at nominal condition
1
Nom. ambient temperature. (max.)
Min. ambient temperature
Nominal inlet air temperature. (max.)
Nominal inlet air pressure
Max. inlet air pressure
Air pressure drop - p
Inlet - Outlet connections
Refrigerant type
Refrigerant quantity
3
Cooling air fan flow
Cooling water flow at 1C (out 3C)
Cooling water flow at 3C (out 4C)
Control of cooling water flow
Maximum water temperature
2
Min. (Max) water pressure
Cooling water connections
Standard Power Supply
3
Nominal electric absorption
Max. electric absorption
Max. level noise at 1 m
Weight
1
The nominal condition refers to an ambient temperature of +25°C with inlet air at 7 barg and +35 °C.
2
Other temperature on request.
3
Check the data shown on the identification plate.