Technical data

31
Compressed Air Applications Manual | Dimensioning Compressed Air Applications Manual | Dimensioning
Table2
Equivalent pipe lengths for fittings and valves
Pipe diameter A 16 20 25 32 40 50 63 75 90 110
Fittings
Elbows 90
0
1.30 0.40 0.50 0.60 0.80 1.00 1.25 1.50 1.80 2.50
Elbows 45
0
0.15 0.20 0.25 0.30 0.40 0.50 0.60 0.75 0.90 1.25
T-piece, flow-through 0.10 0.15 0.15 0.20 0.25 0.35 0.45 0.60 0.75 1.00
T-piece, branch 0.50 0.65 0.80 1.00 1.25 1.50 1.90 2.30 2.90 3.50
T-piece, separation 0.65 0.80 1.00 1.25 1.50 1.80 2.10 2.50 3.10 3.80
Reduction 0.20 0.25 0.30 0.40 0.50 0.70 0.90 1.20 1.50 1.90
Swan-neck section 0.70 0.82 1.00
Valves
Ball valve/
Shutoff valve
0.16 0.18 0.20 0.24 0.28 0.40 0.52 0.65 0.80
Diaphragm valve 0.90 1.20 1.60 2.10 2.60 3.30 4.10 5.00 6.20
You can do this calculation quite easily using our BEKOFLOW
®
calculation program.
Just enter the existing values such as operating pressure, pipe length and flow rate.
The program will then calculate the appropriate pipe dimensions.