Operating instructions

Installation
16 BEKOSPLIT® 11
During the installation, the legal provi-
sions need to be adhered to.
The following points need to be ob-
served in particular:
Move the BEKOSPLIT
®
11 and the
preseparation containers only when
empty, and with suitable means of
transportation (e.g. on pallets.
The BEKOSPLIT
®
11 is top-heavy.
Watch for protruding parts.
Area of installation
Do not install in places where frost
is likely to occur or outdoors!
Sealed floor area or collection basin!
In the event of damage, untreated
condensate or oil must not leak into
the sewerage system or the soil!
Install the BEKOSPLIT
®
11 horizon-
tally on an even, smooth floor.
Tightly screw the oil receiver to the
oil drain of the preseparation con-
tainer using the included connection
kit.
Inlet
Install the condensate manifold (1)>
G1 with a slight downward slope to
the preseparation container at the
wall, use the T-piece (3) as a
branch, and connect with the con-
densate inlet of the pressure relief
chamber (2) via hose line. (Installa-
tion height of the line higher than the
condensate inlet of the pressure re-
lief). The lines must be secured
against loosening, for example by
means of hose clamps (4).
Connect preseparation tank and
BEKOSPLIT
®
11 using the ½ hose
supplied.
Outlet
Fix the water drain hose at the water
outlet of the BEKOSPLIT
®
11, and
supply to the wastewater connection
with a constant slope. Use a siphon
as an odour trap.