Example 3
The requirements of this example are identical to those for
example 2 except for the pulse output. In this example an
outputpulseisrequiredforeachlitreofow.whichisthe
sameasthatbeingproducedbytheowmeter.
Pulse output
5ource direct
The required output pulse from the Rate Totaliser is the
sameaspulseoutputfromtheowmeteri.e.1pulseper
litre. Selecting
direct
inthepulseoutputconguration
menu, results in the output pulse being a synchronous
duplicate of the Rate Totaliser input pulse.
Example 4
This example illustrates how a Rate Totaliser can display
totalowand therate ofow fromastrokesensor ona
reciprocating pump.
Adisplayofthetotaloilowisrequiredinbarrelsofoilwith
a resolution of 0.1. The Rate Totaliser is also required to
display the pump stroke rate in pump strokes per Minute.
Anoutputpulseisrequiredforeachbarreloftotalow.
Each pulse from the pump represents one stroke which is
equivalent to 0.6247 US Gallons.
Summary
Flowmeter K-factor 1 pulse / 0.6247 USG
Required total display 0.0 Barrels
Required rate display 0 Strokes / minute
Pulse output 1 pulse / Barrel
Rate Totaliser Conguration
Flowmeter K-factor
Factor 1
.
0
Each output pulse from the pump represents 1 stroke
therefore no further conversion is required.
Total display
5cale t 67
.
232
dp total 0
.
0
The display is required in Barrels, therefore
5cale t
has
to convert pump strokes to Barrels.
Each pump stroke displaces 0.6247 US Gallons and
there are 42 US Gallons in a barrel.
5Cale t = 42 / 0.6247 = 67.232
Total display resolution of 0.1 barrels is required, hence
decimal pointis positionedbefore the leastsignicant
digit of the display.
Rate display
5cale r 1. 0
dp rate 0
t-ba5e tb-60
Display is required in pump strokes / minute. Each
pulse already represents 1 pump stroke so no further
scaling is required and
5cale r
is set to 1. Rate display
resolution of 1 Stroke is required, hence decimal point
ispositionedafterleastsignicantdisplaydigit
where it
is not visible
.
Selecting a timebase of
tb-60
multiplies the rate display
by 60 to show pump strokes rate per minute.
Pulse output
5ource 5caled
divide 10
The Rate Totaliser outputs a pulse each time the least
signicantdigitofthetotaldisplayisincremented.The
leastsignicantdigitrepresents0.1barrelssothisrate
has to be divided by 10 to produce one output pulse per
barreloftotalow.
15