User Guide

7. Optional 4/20mA output
All BEKA Rate Totalisers can be supplied with a factory
ttedgalvanicallyisolated4/20mAcurrentsinkoutputwhich
can be used for retransmission to other instrumentation.
This output appears as a 4/20mA loop powered transmitter
requiring an external power supply between 5 and 28V.
Theoutputcanbeconguredtorepresentanypartofthe
instrument’s rate or total display.
To prevent a misleading or dangerous current output
afteranychangestotheRateTotaliserconguration,the
4/20mA output must be manually re-enabled before it will
function.
8. Optional dual Alarm outputs
All BEKA Rate Totalisers can be supplied with factory
tteddualalarms.Eachalarmhasagalvanicallyisolated,
solid state single pole, voltage free output that may be
independently congured as a high or low, rate or total
alarm with a normally open or normally closed output.
Congurablefunctionsforeachalarmincludethesetpoint,
alarm delay and silence time. Hysteresis may be applied
to rate alarms.
When the Rate Totaliser’s power supply is turned off
or disconnected, alarm outputs will open irrespective
of whether normally open or normally closed outputs
have been selected. When designing a system it is
recommended that an open output should be selected for
the alarm condition.
Alarm annunciators on the instrument display indicate the
status of each alarm. If an alarm delay or silence time has
beenselectedtheannunciatorwillashduringthedelay
or silence period.
9. Slide-in scale card
All Rate Totaliser’s, except the ‘E’ sufx eld mounting
models, have a slide-in scale card which can be printed
to show the instruments units of measurement. The scale
cardismountedonaexiblestripthatisinsertedintoaslot
at the rear of panel mounting Rate Totalisers and adjacent
totheterminalsoneldmountinginstruments.
New Rate Totalisers can be supplied with a printed scale
card showing requested units of measurement for no
additional charge. If this information is not supplied when
theinstrumentisorderedablankcardwillbettedwhich
can easily be marked on-site.
Inserting scale card in panel Rate Totaliser
13