User Manual
Ta g s
Note:
Alwaysreviewthecandidatesforremovalpriorto removingunu
sedtags,since
removingtagsthatareusedine.g. ascriptcanresultinacorr
uptp roject.
To be able to detect tags used in scripts, a certain syntax must be used. It is
recommended to use the IScriptTag interface within the arguments list for the
ScriptModule,thusenablingtheScriptModule tobeusedandreusedwithout
being locked to a specific tag setup. Use the syntax Globals.Tags.TagName for
direct tag references within scripts and expressions.
If an external editor, e.g. Visual Studio, is used for editing a script, the
cross-reference will not be updated when building the project in iX Developer.
The Remove Unused Tags function will report tags used in these scripts as unused.
For iX Developer to recognize a change made with an external editor, the script file
needs to be opened in iX Developer and provided with just any small change using
thescripteditoriniXDeveloper. Savetheprojectoncemorebeforebuild.
BeijerElectronics, MAEN831P
97